Electra LEX 25 DCI Service Manual page 56

Lex dci series
Hide thumbs Also See for LEX 25 DCI:
Table of Contents

Advertisement

11.7.5
Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST
HST Trend
Decreasing
HST
> 90
SC
85 < HST ≤ 90
D1
82 < HST ≤ 85
SR
80 < HST ≤ 82
SR
78 < HST ≤ 80
Norm
HST ≤ 78
Normal
11.7.6
Outdoor Coil Deicing Protection
11.7.6.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT
<
OAT – 8 AND TLD
Case 2: OCT
<
OAT – 12 AND TLD
Case 3: OCT is Invalid AND TLD
Case 4: Unit is ust switched to STBY AND OCT
j
Case 5: NLOAD
=
0 AND OCT
OCT – Outdoor Coil Temperature
OAT – Outdoor Air Temperature
TLD – Time from Last Deicing
DI – Deicing Interval (Time Interval Between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and
is 40 minutes in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of
deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be
increased. If deicing time is longer then former deicing time, the deicing interval time will be
decreased.
SM LEXDCI 1-E.1 GB
No Change
SC
D2
D1
SR
Norm
> DI
>
30 minutes.
>
DI
< OAT - 8
<
OAT -8
CONTENTS
CONTROL SYSTEM
Increasing
SC
D2
D2
D1
SR
11-7