Tubing Connections - Electra LEX 25 DCI Service Manual

Lex dci series
Hide thumbs Also See for LEX 25 DCI:
Table of Contents

Advertisement

15.

TUBING CONNECTIONS

When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line
at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required.
SM LEXDCI 1-E.1 GB
TUBE (Inch)
¼"
TORQUE (Nm)
Flare Nuts
11-13
Valve Cap
13-20
Service Port Cap
11-13
1.
Valve Protection Cap-end
2.
Refrigerant Valve Port (use Allen wrench to open/close)
3.
Valve Protection Cap
4.
Refrigerant Valve
5.
Service Port Cap
6.
Flare Nut
7.
Unit Back Side
8.
Copper Tube
CONTENTS
TUBING CONNECTIONS
⅜"
½"
⅝"
40-45
60-65
70-75
13-20
18-25
18-25
11-13
11-13
11-13
¾"
80-85
40-50
11-13
15-1