3.1

Malfunction management

Malfunction management records the last 15 malfunctions with date and time stamps. In addition, "System Errors"
are recorded in "Error Memory" when the malfunction occurs. This history can be selected and cleared only by the
service technician level 2 password.
A malfunction will display a text message in the Starting Menu. When a failure occurs the relay defined in the
system setup as "Failure relay" is activated. The red LED in the front of the Controller flashes.
During the malfunction of a sensor point (SP) stages that are assigned for sensor failure are activated. Relays that
are assigned to these stages perform as if the stage has been exceeded. These assignments are programmed in
the menu "SP Setup".
3.1.1

Acknowledge a malfunction

Note:
Resetting a malfunction is only possible if the problem is corrected.
SP 01 < 3mA
Error Cleared
Malfunction Cleared
3.1.2

History error summary

The code level 2 password can open the menu "Hist Error Sum" in the main menu "System Errors".
The last 15 error messages are listed for the service technician even if they have already been reset. These error
messages can be deleted individually
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
System Errors
SP 01 < 3mA
05.02
10.38
SP 01 < 3mA
Reset ??
Error still
or
exists
Problem not corrected
Reset not possible
Fax (858) 578-4633 & (888) FX INTEC
Select Menu "System Errors"
Example: Failure SP 01 < 3 mA
Malfunction Reset?
Malfunction Reset
Specification subject to change without notice.
www.inteccontrols.com
Page 08