3.7.10 Activation Of Expansions Modules - Intec MGC2-16 User Manual

Multi-point controller
Table of Contents

Advertisement

PolyGard
Multi-Point Controller
®
User Manual - MGC2-16

3.7.10 Activation of expansions modules

The Gas Controller can manage, up to five expansions modules (EP-02). Each EP-02 has four analog inputs and
five alarm relays and two analog outputs. Each attached EP-02 is announced in this menu. The Controller checks
the communication to the registered EP-02 modules and shows a fault signal in case of a communication error. To
recognize the position of the EP-02 modules a module address is assigned to each module by the address
selector. See table.
The table shows the assignment of the MP and relay numbers to the individual modules.
Symbol Description
EP- Module No 1 active
EP- Module No 2 active
Not
EP- Module No 3 active
active
EP- Module No 4 Not active
EP- Module No 5 Not active
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Default
Function
Status
Active
= EP announced.
Not active
= EP not announced
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Page 23
Module
Relay
SP No.
Addr.
No.
1
06 to 10 05 to 08
2
11 to 15 09 to 12
3
16 to 20 13 to 16
4
----
-----
5
----
-----
Specification subject to change without notice.
Output
No.
03 to 04
05 to 06
07 to 08
-----
-----
MGC2-16
Printed in USA 131119