Menu Sp Setup - Intec MGC2-16 User Manual

Multi-point controller
Table of Contents

Advertisement

PolyGard
Multi-Point Controller
®
User Manual - MGC2-16
3.6

Menu SP Setup

Display and Change Parameters, Assign Stage value, Assign relays to stages and activate each Sensor Point
(SP).
SP Setup
SP 01
active
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
(Main Menu)
(Selection of a sensor point)
SP Mode
Activate or deactivate SP
active
See 3.6.1
SP Type
Define Type
NH3
See 3.6.2
Measuring range
Define Measuring range
300 ppm
See 3.6.3
SP-Signal
Define signal type of transmitter
linear
See 3.6.4
Stage 1
Define Stage/Setpoint 1
100 ppm
See 3.6.5
Stage 2
Define Stage/Setpoint 2
100 ppm
See 3.6.5
Stage 3
Define Stage/Setpoint 3
200 ppm
See 3.6.5
Stage 4
Define Stage/Setpoint 4
200 ppm
See 3.6.5 Stage/Setpoint
Stage 5
Define Stage/Setpoint 5
300 ppm
See 3.6.5
Hysteresis
Hysteresis
15 ppm
See 3.6.5
Delay ON time
Set Delay ON time
0 s
See 3.6.6
Fax (858) 578-4633 & (888) FX INTEC
Specification subject to change without notice.
www.inteccontrols.com
Page 14
MGC2-16
Printed in USA 131119