Specifications Mgc2-16 - Intec MGC2-16 User Manual

Multi-point controller
Table of Contents

Advertisement

PolyGard
Multi-Point Controller
®
User Manual - MGC2-16
7

Specifications MGC2-16

Electrical
Power supply
Power Consumption
RF/RMI proteced
Type of control
General
Analog Input
Analog reading
Power supply for Analog inputs
Stage level / setpoint
- hysteresis/ switching differential
Digital inputs
Relay outputs (R1-R20) w/ status LEDs
- each stage level (S1-S5)
- sensor fail-safe
Time delay switching
VDC output supply
Analog output
Audible alarm
Alarm acknowledgement
User Interface
Keypad type
Touch buttons
Status LED's
Digital display
- unit display
Environmental
Permissible ambient
- working temperature
- storage temperature
- humidity
- working pressure
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
120 VAC (90 to 230 VAC) 50/60Hz
resettable breaker
50 VA, max.
4.0 W @ 3 ft. (1 m) radiated
Five-stage (S1 to S5) control, assignable up to
twenty (20) binary/relay output, i.e.
Low-med-high-fault / fail-horn*, or low1-low 2-
med1-med2-high, or any other combinations
(* = horn/audible alarm built-in and factory pre-
configured to relay output "R20")
sixteen (16), 4 - 20 mA
Current and mean (average) value
24 VDC max. 50 mA / channel
Field adjustable over full range, five (5) per
analog input, assignable to current or mean
(average) value
Selectable for each sensor point
Four (4) each can be individually assigned to
any relay (R1..R20). Digital inputs are used for
remote audio/visual alarm reset
twenty (20) SPDT, 8 A, 24 VAC/VDC -250 VAC
contact resistance 100 m, max.
Assignable to any relay
Assignable to any stage level
Selectable for make and brake of each sensor
point (SP1 to SP16) 0-9,999 seconds
24 VDC, 0.5 A fused
eight (8) independent 4 - 20 mA signal, 500 
max. load, selectable as low, high or averaging
of sensor inputs
90 db, enabled or disabled, selectable;
assignable to stage level S1, S2, S3, S4 or S5
Menu-driven and system reset function for
latched relays
See 2.1 "Description Keypad User Interface"
Six (6)
Yellow: Alarm; Red: Fault (fail)
Liquid Crystal Display (LCD), two lines, 16
characters per line, 1 digit resolution, backlit
Menu selectable, per sensor;
ppm, %v/v, %LEL; °F or % RH
23 °F to 104 °F (-5 °C to+ 40 °C)
-4 °F to 104 °F (-20 °C to + 40 °C)
15 to 95 % RH non condensing
Atmospheric ± 10%
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Page 33
Specification subject to change without notice.
Printed in USA 131119
MGC2-16