Section 3-4: Venting Components

Connection and installation of the vent components
should adhere to the following guidelines:
Use any combination of rigid and flex pipe as required
and in any orientation (Male connectors can face in
any direction).
Flex sections may be stretched up to 50% of their total
length (e.g. a 24" section maybe stretched to 36").
Connect all vent sections using a minimum of three
sheet metal screws on the outer pipe flue.
Ensure the pipe ends male to female slide in a
minimum of 1 1/2" of overlap.
Ensure all horizontal runs are supported with a
minimum of 3 supports per 10' of venting.
When hanging/ supporting venting, ensure that 1"
clearance is maintained on sides and bottom of
vent runs and 2" above horizontal vent runs to any
combustible material.
Rigid pipe may be cut less than half way from the
female end only.
Ensure when cutting sections of rigid pipe to maintain
integrity of internal supports.
Place the springs, supplied with the pipe kit, between
the outer and inner pipes to keep the pipes separate
and avoid any possible hot spots.
Montigo recommends the use of a flex section for the
final pipe connected directly to the fireplace offering
greater flexibility of installation and absorption of
movement.
Firestops must be installed as required by National
& local codes .
Montigo recommends that all exterior corners and
joints be sealed with exterior caulking. However, we
encourage you to consult your Building Envelope
Engineer or Waterproofing Consultant for further
recommendations.
IMPORTANT:
Please Refer to your Building Envelope
Engineer or Waterproofing Consultant
for a review of ALL penetrations through
exterior walls or the roof.
XG0218 - 160215
Installation
A - Termination
B - Frame Kits
C - Flex Sections
(5/8 Vent)
D - Rigid Sections
(5/8 Vent)
(5/10 Vent)
E - Elbows
(5/8 Vent)
(5/10 Vent)
F - Support Ring & Plate
G - Firestop
H - Roof Flashing
I - Heat Shield
J - Heat Guard
K - Reducing Collar
L - Through the Wall
Venting Kit
PL52DF* Indoor Gas Fireplace
RTO4F (5/10 Vent)
PVTK1SS (5/8 Vent)
MSR
(Stucco Frame)
MOSR
(Stucco Frame)
BSR-4
(4" Brick Frame)
BSR-6
(6" Brick Frame)
PFL - 1
(12" f/f Section)
PFL - 18 (18" f/f Section)
PFL - 2
(24" f/f Section)
PFL - 3
(36" f/f Section)
PFL - 4
(48" f/f Section)
PFL - 6
(72" f/f Section)
PXT - 5
(5" f/f Section)
PXT - 10 (10" f/f Section)
PXT - 20 (20" f/f Section)
PEXT - 1 (12" f/m Section)
PEXT - 2 (24" f/m Section)
PEXT - 3 (36" f/m Section)
PEXT - 4 (48" f/m Section)
PEXT - 6 (72" f/m Section)
RXT - 10 (10" f/f Section)
RXT - 20 (20" f/f Section)
REXT - 1 (12" f/m Section)
REXT - 2 (24" f/m Section)
REXT - 3 (36" f/m Section)
REXT - 4 (48" f/m Section)
REXT - 6 (72" f/m Section)
PEL-90MM (m/m 90º Elbow)
PEL-90FF ( f/f 90º Elbow)
PEL-90FM ( f/m 90º Elbow)
PEL-45FM ( f/m 45º Elbow)
REL-90MM (m/m 90º Elbow)
REL-90FF ( f/f 90º Elbow)
REL-90FM ( f/m 90º Elbow)
REL-45FM ( f/m 45º Elbow)
PSPXT-8
FS-8
PRF-7
(1/12 - 7/12 pt.)
PRF-12
(7/12 - 12/12 pt.)
RHS101
RHS102
RHS104
MTKOG
RC108
RFVKO1F
Page 17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pl52dfl-i

Table of Contents