Fault Shutdowns
Code
Description
Frequency
Underfrequency
Low
shutdown occurs
Shutdown
when the
governed
frequency falls
below the default
setting of the
system's
frequency setpoint.
Locked
Overcrank (locked
Rotor
rotor) shutdown
Shutdwn
Oil Pres Low
Low oil pressure
Shutdwn
shutdown occurs if
a low oil pressure
condition exists.
Note: The low oil
pressure shutdown
does not protect
against low oil
level. Check the
oil level at the
engine.
Over Crank
Overcrank
Shutdwn
shutdown occurs
after 3
unsuccessful
starting attempts.
Sea Pressur
Low seawater
Low
pressure
Shutdwn
shutdown occurs
after a loss of
seawater
pressure is
detected.
Volts xx--xx
Overvoltage
High
shutdown occurs if
Shutdwn
the voltage
exceeds the
default setting of
the voltage
regulator setpoint.
Volts xx--xx
Undervoltage
Low
shutdown occurs
Shutdwn
if the voltage falls
below the default
setting of the
voltage regulator
setpoint.
Figure 2-9 Advanced Digital Control IId Fault Shutdown
TP-6772
2/14b
Sensing
State(s)
Mechanism
Detected
Alternator
Post starting
output
aid, running,
cooldown
Frequency
Cranking
over AC
voltage
Analog or
Post starting
digital input
aid, running,
cooldown
Fail to start
ECM start,
starting aid,
cranking,
crank pause
Digital input
Post starting
aid, running,
cooldown
Alternator
Post starting
output
aid, running,
cooldown
Alternator
Post starting
output
aid, running
cooldown
Inhibit
Delay
Time
Time
Trip Point Check
10 sec
10 sec
AC
frequency
below 90%
of the
systems
frequency
0 sec
3 sec
3 sec.
Engine
speed is
below 10
rpm and
the oil
pressure is
below
crank oil
pressure
(69 kPa)
1 sec
10 sec
At or below
117 kPa
0 sec
7 sec on/
3 crank
15 sec off
cycles.
Controller
goes into
the
cranking
state 3
consecutive
times
without
going into
post
starting aid
10 sec
5 sec
Switch
closes
(shorted-to-
ground)
0 sec
2 sec
xx--xx AC
voltage
exceeds
120% of
the AC
system
voltage
0 sec
10 sec
xx--xx AC
voltage
below 80%
of the AC
system
voltage
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service if
problem continues.
Contact an authorized
distributor/dealer for service if
problem continues.
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
Check the fuel supply and battery.
Also check for loose connections.
Contact an authorized
distributor/dealer for service if
problem continues.
Check for a clogged seawater
intake or sea strainer.
Check for a damaged seawater
pump impeller.
Contact an authorized
distributor/dealer for service if
problem continues.
Reduce the load and restart the
generator set.
Check the F1 fuse.
Contact an authorized
distributor/dealer for service if
problem continues.