Kohler 6EKOD Operation Manual page 26

Marine generator sets
Hide thumbs Also See for 6EKOD:
Table of Contents

Advertisement

Fault Shutdowns
Code
Description
AC Sens
The loss of AC
Loss Low
voltage shutdown
Shutdwn
occurs when the
controller does
not detect the
nominal generator
AC output voltage
for more than 3
seconds after
crank disconnect.
Aux Input
Auxiliary fault
Shutdwn
input shutdown.
Note: Input from a
customer-supplied
switch that closes
when the fault is
active.
Coolant
High coolant
Temp High
temperature
Shutdwn
shutdown occurs if
the engine coolant
temperature
exceeds the
default setting.
Note: The high
engine temp.
shutdown
functions only
when the coolant
level is in the
operating range.
Eng Speed
High engine
High
speed shutdown
Shutdwn
occurs if the
engine speed
exceeds the
default setting.
Eng Speed
Low engine speed
Low
shutdown occurs
Shutdwn
if the engine
speed falls below
the default setting.
Exh Temp
High exhaust
High
temperature
Shutdown
shutdown occurs if
the engine exhaust
temperature
exceeds the
default setting.
Frequency
Overfrequency
High
shutdown occurs
Shutdwn
when the
governed
frequency exceeds
the default setting
of the system's
frequency setpoint.
26
Section 2 Operation
Sensing
State(s)
Mechanism
Detected
Frequency
Post starting
over AC
aid, running,
voltage
cooldown
Digital input
Auto, fault,
start delay,
ECM start,
starting aid,
cranking,
crank pause,
post starting
aid, running,
cooldown
Analog input
Post starting
aid, running,
cooldown
Frequency
Post starting
over AC
aid, running,
voltage
cooldown
Frequency
Post starting
over AC
aid, running,
voltage
cooldown
Digital input
Auto, fault,
start, ECM
start, starting
aid, cranking,
crank pause,
post starting
aid, running,
cooldown
Alternator
Post starting
output
aid, running,
cooldown
Inhibit
Delay
Time
Time
Trip Point Check
10 sec
3 sec
AC voltage
reached AC
system
voltage and
then drops
below 5%
of the trip
point for
low AC
voltage
fault/
shutdown
0 sec
2 sec
Switch
closes
(shorted-to-
ground)
15 sec
5 sec
Coolant
temperature
at or above
110_ C
(230_ F)
0 sec
300 ms
Engine
speed
exceeds
115% of the
rated speed
0 sec
3 sec
Engine
speed falls
below 85%
of the rated
speed
0 sec
2 sec
Switch
closes
(shorted-to-
ground)
10 sec
5 sec
AC
frequency
exceeds
110% of the
systems
frequency
Contact an authorized
distributor/dealer for service.
Check the cause of the auxiliary
fault.
Check for a low engine coolant
level.
Check seawater pump impeller,
strainers, and seacock.
Contact an authorized
distributor/dealer for service if
problem continues.
Contact an authorized
distributor/dealer for service.
Check the wiring to the sensor.
Check for a clogged seawater
intake or sea strainer.
Check for a damaged seawater
pump impeller.
Check the exhaust system, see
Section 3.5.
Contact an authorized
distributor/dealer for service if
problem continues.
TP-6772
2/14b