Freeze-Up Protection Control; Heating Peak-Cut Control - Daikin FTX50GV1B Service Manual

Hide thumbs Also See for FTX50GV1B:
Table of Contents

Advertisement

Control Specification
3.6

Freeze-up Protection Control

During cooling operation, the signal sent from the indoor unit controls the operating frequency
limitation and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is
divided into zones.)
The operating frequency limitation is judged with the indoor heat exchanger temperature.
3.7

Heating Peak-cut Control

During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
37
13˚C
Reset zone
A˚C
Up zone
B˚C
Keep zone
C˚C
Dropping zone
0˚C
Stop zone
A (°C)
B (°C)
C (°C)
7
5
B˚C
C˚C
D˚C
Indoor heat exchanger
thermistor temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
A (°C)
B (°C)
C (°C)
65
56
Indoor heat exchanger
thermistor temperature
3
D (°C)
E (°C)
55
53
51
SiBE041029EB
(R14718)
Stop zone
A˚C
Dropping zone
Keep zone
Up zone
E˚C
Reset zone
(R14645)
Control
Function and Control