Troubleshooting
Troubleshooting
Check No.01
Refer to P.93
Check No.12
Refer to P.94
Change for a specified amount of
fresh refrigerant.
61
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Any thermistor
disconnected?
NO
Stop valve closed?
NO
Check for refrigerant shortage.
Oil oozing at relay
pipe connections?
NO
Oil oozing at internal
piping?
NO
Check No. 12
Electronic expansion valve
functioning?
YES
Refrigerant shortage error
again?
YES
Check No. 01
Check the thermistors.
OK
Replace the outdoor unit PCB.
Error again?
YES
YES
∗ Discharge pipe thermistor
∗ Indoor or outdoor heat exchanger thermistor
∗ Room temperature thermistor
∗ Outdoor temperature thermistor
YES
YES
YES
Compressor vibrating
too much?
YES
NO
NO
NG
NO
SiBE041029EB
Replace the thermistor(s)
position.
Open the stop valve.
Repair the pipe flare or
replace the union.
NO
Check the pipes for
improper contact and
correct them as required.
Replace the cracked pipe.
Check the power transistor
harness for loosening.
Correct it as required. Also
replace the cracked pipe.
Replace the electronic
expansion valve.
Completed.
Replace the defective
thermistor(s).
Completed.
Replace the compressor.
(R19373)
Service Diagnosis