Boiler Location & Clearances - Worcester GREENSTAR UTILITY 18/25 Instruction Manual

Floor standing oil fired condensing boiler conventional flue & room sealed flue
Table of Contents

Advertisement

8 716 106 256 C 03.10
30/3/10
a: RECOMMENDED
IN STALLATION C LEARANC E S
b: ANNUAL SERVICE CLEARANCES
c: MAINTENANCE & REPAIR
CLEARANCES
MINIMUM AIR VENT AREA (cm
1 Internal air to and from a space/room inside the building. 2 External air to and from directly outside the building.
Conventional flue:**
Internal 1 ventilation
High
Low
Model Level
Level
18/25
275
413
14
BOILER LOCATION & CLEARANCES
14:24
Page 14
570mm
1200mm
300mm
100mm
100mm
600mm
380mm
1200mm
10mm
5mm*
5mm*
600mm
380mm
1200mm
300mm
5mm*
5mm*
600mm
2
) FOR APPLIANCES INSTALLED IN A COMPARTMENT:
Room Sealed flue:**
External 2 ventilation
Internal 1 ventilation
High
Low
High
Level
Level
Model Level
138
275
18/25
275
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR UTILITY 18/25
BOILER LOCATION &
CLEARANCES
• This boiler is only suitable for installing
internally within a property at a suitable
location onto a fixed rigid surface of the same
size as the boiler and capable of supporting
the boiler weight.
• The boiler must be installed on a flat level
surface to ensure condensate does not enter
the primary heat exchanger.
• The boiler is not suitable for external
installation unless a suitable enclosure is
provided.
• Roof space installations must fully conform to
BS 5410 part 1 section 4.6.9.
Open flue model (CF):
• In order to ensure clean and efficient
combustion an adequate supply of air must
be delivered to the combustion chamber.
• To provide sufficient air a suitable inlet must
be provided into the room or space in which
the boiler is situated, minimum size 138cm
for 18/25kW appliances.**
An air brick or other form of continuous air
supply may have to be built into the installation
in order to ensure an adequate supply of air.
• If the appliance is to be installed in a confined
space or compartment two air vents are
required, one at high level and one at low level.
The minimum free area of each vent is
shown opposite and depends whether the
air is taken from another room or from
outside the building.
• Where the air is taken from another room that
room must contain an air inlet as described
above.
Room sealed balanced flue model (RS):
The appliance does not require a separate vent
for combustion air.
• Installation in cupboards or compartments
require permanent vents for cooling purposes,
one at high level and one at low level, either
direct to outside air or to a room.
• Both vents must pass to the same room or be
on the same wall to the outside air.
The minimum air vent free area is given in the
table opposite.
a: INSTALLATION CLEARANCES:
Diagram ( a ) shows the minimum space
recommended to install the boiler only.
b: SERVICE CLEARANCES:
Diagram ( b ) shows the minimum space
required to carry out an annual service.
c: MAINTENANCE & REPAIR CLEARANCES:
The appliance is suitable for an under worktop
installation providing that the worktop above the
boiler (min 10mm clearance) is removable for
maintenance and repair and the front of the
boiler is not enclosed.
External 2 ventilation
* Remove the flue 'knock-out' panel sections if
Low
High
Low
this clearance is less than 75mm.
Level
Level
Level
** Due to changes to BS 5410 and modern
138
138
275
building design, these figures no longer
incorporate the adventitious ventilation allowance.
2
8 716 106 256C (03/2010)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents