PROBLEM
FAULTY BOILER
OPERATION:
Noisy operation
Boiling
Short Cycling
OIL SMELLS:
44
FAULT FINDING
14:24
Page 44
CAUSE
REMEDY
Pump noise from air in pump or
Bleed air from pump or replace pump
worn pump
Worn motor bearings
Replace motor
Fan out of balance
Replace fan
Faulty boiler thermostat
Replace if necessary
Short circuit boiler thermostat
Temporarily take out of circuit to check
Thermostat bulb not fully home in
Ensure bulb is pushed fully home
pocket
No primary water circulation
Check system / circulating pump
Burner rating incorrect
Correct burner rating
Boiler thermostat differential
Replace boiler thermostat
incorrect
External controls not operating
Check and correct external controls
correctly
Blocked flue, fumes on startup
CF - Check flue with gauge and check
seals/gaskets
RS - Check seals/gaskets
Oil soaked boiler, faulty burner
Rectify burner operation and lockouts
operation, numerous lockouts
Odour in boiler room, oil leaks
Rectify oil leaks, replace components if
from pipework, flexible hoses
necessary
connections
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR UTILITY 18/25
FAULT FINDING
8 716 106 256C (03/2010)