7638135 - v.02 - 13082015
No.
Description
5
–
6
–
7
–
8
–
9
–
Caution
If possible, use the pump modulation signal. This provides the
most accurate pump control.
In positions 3 to 9 the control PCB receives no signal from the
boiler and the boiler responds as in position 0.
If the automatic burner unit does not support pump modulation,
the pump will behave as an on/off pump.
Select the type of signal that controls the pump using the rotary knob SW2
on the PCB. See table below.
No.
Description
0
0–10 V (Wilo pump)
1
0–10 V (Grundfoss pump)
2
PWM
3
4–20 mA
4
–
5
–
6
–
7
–
8
–
9
–
Caution
In positions 4 to 9 the control PCB sends no signal to the pump
and the pump will not start up.
7 Appendix
19