Fig.3
210-160 - 210-200
7638135 - v.02 - 13082015
Tab.9
Values at full load for
G20
210-80
210-120
210-160
210-200
(1) Nominal value
Tab.10 Checking/setting values for O
Values at full load for
G31
210-80
210-120
210-160
210-200
(1) Nominal value
4. If the measured value is outside of the values given in the table, cor­
rect the gas/air ratio.
Note
The 210-80 and 210-120 boilers are equipped with a restrictor on
the gas valve unit. They can therefore only be set to part load.
5. Using the adjusting screw, set the percentage of O
type being used to the nominal value. This should always be inside
the highest and lowest setting limit. The direction in which the ad­
justment screw must be turned to increase or decrease the gas flow
is indicated on the gas valve unit.
6. Check the flame through the inspection window.
Note
The flame must not blow off.
AD-3000113-01
Checking/setting values for O
1. Set the boiler to part load.
2. Measure the percentage of O
3. Compare the measured value with the checking values in the table.
Tab.11 Checking/setting values for O
Values at part load
for G20
210-80
210-120
210-160
210-200
(1) nominal value
Checking/setting values for O
O
%
(1)
2
3,9 - 5,2
- 6,5
(1)
3,9 - 5,2
- 6,5
(1)
4,3 - 5,2
(1)
4,3 - 5,2
(1)
O
%
(1)
2
4,7 - 5,7
- 6,7
(2)
4,7 - 5,7
- 6,7
(2)
4,9 - 5,7
(2)
4,9 - 5,7
(2)
/CO
2
/CO
2
2
O
%
(1)
2
3,4 - 4,3
(1)
3,4 - 4,3
(1)
3,4 - 4,3
(1)
3,4 - 4,3
(1)
4 Commissioning
at full load for G20
2
CO
%
(1)
2
8,1 - 8,8
- 9,5
(1)
8,1 - 8,8
- 9,5
(1)
8,8
- 9,3
(1)
8,8
- 9,3
(1)
at full load for G31
2
CO
%
(2)
2
9,3 - 10,0
- 10,7
(2)
9,3 - 10,0
- 10,7
(2)
10,0
- 10,5
(2)
10,0
- 10,5
(2)
/CO
for the gas
2
2
at part load
2
in the flue gases.
at part load for G20
2
CO
%
(1)
2
9,3
- 9,8
(1)
9,3
- 9,8
(1)
9,3
- 9,8
(1)
9,3
- 9,8
(1)
13