Page 1
PACKAGED STANDBY SYSTEM INSTALLATION AND OPERATORS MANUAL ULPSS8B2W/E 075-00 60706-2...
Page 2
The warranty listed in the manual describes the number and other vital information here. If you what you can expect from WINCO should you need should ever need to contact us on this unit it will help service assistance in the future.
SAFETY INFORMATION 2. FIRE HAZARD Natural gas and L.P. present a hazard of possible explosion and/or fire. This engine generator set has been designed and a. Do not refuel when the engine is running or manufactured to allow safe, reliable performance. hot.
Page 4
UL Automatic Transfer Switch Sizes DESCRIPTION UNIT LINE SIDE GENERATOR CONTACTOR SIDE CONTACTOR The package standby system includes all times ULPSS8B2W 00 AMPS 00 AMPS necessary for a completely automatic standby power 200 AMPS 200 AMPS system as standard equipment.
Page 5
SPECIFICATIONS “Concealed Damage” is understood to mean dam- age to the contents of a package which is not evi- dent at the time of delivery by the carrier, but wheich GENERATOR is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in tran- MODEL WATTS* VOLTS...
Page 6
ENGINE GENERATOR SET MOUNTING critical; failure to provide the proper pressure can cause many problems ranging from a unit that will WARNING - Personal Injury not start to causing damage to the fuel system. The enclosures on these units can become very These units are normally tested on Natural Gas and hot adjacent to the exhaust areas.
NATURAL GAS or LP VAPOR PIPE SIZE Size of pipe nomally required for generators operat- ing on NATURAL GAS or LP VAPOR. FEET SIZE OF PIPE up to 25 FT* 3/4 “ Pipe 25 - 100 FT* 1” Pipe over 100 FT* Use a two regulator system.
BCI Group MINIMUM NO LOAD LINE PSI 7-11 IN 7-11 IN CCA Rating 4-6 OZ 4-6 OZ ULPSS8B2W FULL LINE PSI 7-11 IN 7-11 IN LOAD 4-6 OZ 4-6 OZ Installation and servicing of batteries must be per- formed or supervised only by personnel knowledge- able of batteries and the required precautions.
* Where electrolyte contacts the skin, wash off im assembly. All connections must be clean and tight. mediately with water. Check the electrolyte (fluid) in the battery periodi- * If electrolyte contacts the eyes, flush thoroughly cally to be sure it is above the plates. Never allow and immediately with water and seek immediate the battery to remain in a discharged condition.
Page 11
These last two connections will be discussed later in more detail. NOTICE - CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNEC- WINCO UL ATS (ASCO 165) TIONS TO TERMINALS OF A CLASS 2 CIRCUIT. See the ASCO installation manual for additional ******************...
Page 12
Because of the many different types of service, is numbered through 9. These terminals will feeder, and distribution equipment, no specific wiring accept # 22 - # 4 AWG stranded wire. It is recom- instructions can be provided. It is, however, recom- mended that you use # 6 AWG for distances up mended that copper wire be used.
Page 13
PROCEDURE . Turn on the preferred source (utility) circuit breaker. The utility source acceptable light should Engine Generator Set only now come on as well as the transfer switch on utility light. If these lights fail to come on recheck your The engine control module (ECM) is manufactured incoming power to insure you have 240 volts nomi- by Deep Sea Electronics.
Page 14
5. About 5 seconds after the generator (alter- ENABLING THE EXERCISER CIRCUIT nate source) acceptable light comes on, the auto- Press and hold the Automatic Generator Exerciser matic transfer switch should transfer the load from the utility to the generator. At that time the Transfer button until the light goes off, the light flashes then Switch on generator light should come on.
PREVENTIVE MODULE DISPLAY MAINTENANCE TIMER ICON When the module is controlling the engine (start- ing and stopping) an animated timer icon will be Reasonable care in preventive maintenance will displayed in the icon area to indicate that a timer is insure high reliability and a long life for the engine active, for example cranking time, crank rest, etc.
Page 16
DSE 3110 CONTROL STOP/RESET (Red Button) This button places the module into its “Stop/ Reset” mode. This will clear any alarm conditions for which the triggering criteria have been removed. If the engine is running and the module is in Stop mode, the module will automatically instruct the changeover device to unload the generator.
Page 17
FRONT PANEL CONFIGURATION This configuration mode allows the operator limited customizing of the way the module operates. Use the module’s navigation buttons to traverse the menu and make value changes to the parameters. . ACCEPT button. . ACCEPT button. 2. NEXT PAGE button. 2.
DSE 3110 CONTROL FAULT CODES DESCRIPTION Auxiliary inputs can be user configured and will display AUXILIARY INPUTS the message as written by the user. The engine has not fired after the preset number of start FAIL TO START attempts The module has detected a condition that indicates that the engine is running when it has been instructed to stop.
Page 19
ENGINE GENERATOR SET LAYOUT ULPSS8B2W/E 075-00 60706-2...
WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product. At WINCO’s option, material found to be de- fective in material or workmanship under normal use and service will be repaired or re- placed.