FUNCTION SETTING

12 3 4
CENTRALLY CONTROLLED
ON OFF
CLOCK
CHECK
˚C
STAND BY
ERROR CODE
DEFROST
TEMP.
F
E
TIMER SET
PAR-20MAA
G
C D
1
3
2
3
4
Wired type
1Hr.
Changing the power voltage setting
˚C
• Be sure to change the power voltage setting depending on the voltage
FILTER
CHECK MODE
TEST RUN
FUNCTION
NOT AVAILABLE
ON/OFF
Selecting functions using the wired remote controller
FILTER
A
CHECK TEST
B
[Operating instructions] (entering settings with a wired remote controller)
1 Go to the function setting mode.
2 Setting the refrigerant address
FUNCTION
*
FUNCTION
FUNCTION
3 Setting the unit number
FUNCTION
1
Mode number
2
Setting number
3
Refrigerant address
4
Unit number
used.
1 Check the function selection setting.
2 Switch to function setting mode. w
(Press A and B at the same time
with the remote controller stopped.)
3 Specify refrigerant address 00 (outdoor unit)
4 Specify unit No. 00. (indoor unit)
(Use C and D.)
5 Enter the setting.
(Specified indoor unit:
(Press E.)
BLOW operation)
6 Select mode No 02
(room temperature detection position).
7 Select setting No. 03 (remote controller fixed).
(Use F and G.)
Example:
8 Enter the setting.
Selecting room temperature
(Press E.)
detection position
NO
Finished
YES
Function selection end screen
10
(Press A and B at the same time.)
Switch OFF the remote controller.
Press the A FILTER and B TEST RUN buttons simultaneously and hold
them for at least 2 seconds. FUNCTION will start to flash. The refrigerant
address display will start to flash momentarily (see diagram 1).
Use the C
(TIMER SET) button to set the refrigerant address
(3) to 00 (see diagram 2). Press
decrease it.
00 is the typical setting. When operating in a group configuration, use
the correlating refrigerant address (see the technical manual for details
on setting the refrigerant address for a group). The refrigerant address-
es must be set in order when performing the following operation.
If the unit stops two seconds after the FUNCTION display starts to flash
or [88] starts to flash in the room temperature display, a transmission
problem may have occurred. Check to see if there is some source of
transmission interference (noise) nearby.
If you make a mistake during any point of this procedure, you can quit
the function setting mode by pressing 8 once and then return to step
1.
Press D (CLOCK ON OFF) and [--] will start to flash in the unit number
(4) display (see diagram 3).
Use the C
(TIMER SET) button to set the unit number to 00
(see diagram 3). Press
Unit number 00 = the function setting selection for the entire refrigerant
system.
76
w For modes 15 and higher,
press J and B at the same
time.
YES
NO
Change refrigerant
address unit No.
9
to increase the value or
to increase the value or
to decrease it.
to