Mitsubishi Electric PKA-RP1.6GAL Service Technical Manual page 49

Table of Contents

Advertisement

Control modes
3-1. Normal control
3. LEV(A)
3-2. Compulsory step-up
3-3. Stop control
Opening pulse will vary among steps (1 to 3) according to air conditioner's
operating status.
• Control timing: Once every 5 minutes after 3 or 7 minutes have passed since
the compressor started.
• LEV opening pulse for each step:
Step
RP1.6VHA RP2VHA RP2.5VHA
RP3VHA
1
195
200
150
2
300
300
300
3
480
480
480
• Requirement for step-up
LEV opening pulse will step up when any of following conditions is satisfied.
(1) The discharge temperature (TH4) is 100: or more
(2) The outdoor condenser/evaporetor temperature (TH6) is 57: or more
(3) The discharge super heat temperature is 50: or more Super heat
temperature = Discharge temperature (TH4) - Outdoor condenser/evaporetor
temperature (TH6)
(4) The sub cool temperature is 12: or more
Sub cool temperature = Outdoor condenser/evaporetor temperature (TH6)
- Outdoor liquid pipe temperature (TH3)
• Requirement for step-down
LEV opening pulse will step down when any of following conditions is satisfied
and any of step-up conditions are NOT satisfied.
(1) The discharge temperature (TH4) is 90: or less.
(2) The outdoor condenser/evaporetor temperature (TH6) is 52: or less.
(3) The discharge super heat temp. is 40: or less.
Super heat temperature = Discharge temperature (TH4) - Outdoor
condenser/evaporetor temperature(TH6)
(4) The sub cool temperature is 3: or less.
Super heat temperature = Outdoor condenser/evaporetor temperature
(TH6) - Outdoor liquid pipe temperature (TH3)
• The step does not change if neither step-up conditions nor step-down
conditions are satisfied.
When any of the following conditions is satisfied, the step will be forced to 3.
(1) The discharge temperature (TH4) is 110: or more.
(2) The condenser/evaporetor temperature (TH6) is 62: or more.
When the LEV is being stopped, the step will be set to 3.
Control details
RP4VHA RP5VHA RP6VHA RP4VHA
200
220
220
220
220
300
300
300
300
260
480
480
480
480
480
49
Remarks
RP5VHA
RP6VHA
1
1
1
220
220
260
260
480
480

Advertisement

Table of Contents
loading

Table of Contents