Mitsubishi Electric PKA-RP1.6GAL Service Technical Manual page 71

Table of Contents

Advertisement

SW2 setting
Outdoor unit setting information
ON
1
2 3 4 5 6
Indoor pipe temperature / Liquid
(TH2(1))
ON
Indoor 1
– 39~88
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
(TH5(1))
ON
Indoor 1
– 39~88
1
2 3 4 5 6
Indoor pipe temperature / Liquid
(TH2(2))
ON
Indoor 2
– 39~88
1
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
(TH5(2))
ON
Indoor 2
– 39~88
1
2 3 4 5 6
Indoor room temperature (TH1)
8~39
ON
1
2 3 4 5 6
Indoor setting temperature
ON
17~30
1
2 3 4 5 6
Indoor control status
ON
1
2 3 4 5 6
Outdoor control status
ON
1
2 3 4 5 6
Display detail
71
Explanation for display
• The tens digit (Total display for applied setting)
Setting details
Display details
H·P / Cooling only
0 : H·P
Single phase / Three phase
0 : Single phase 2 : Three phase
• The ones digit
Setting details
Display details
Defrosting switch
0 : Normal
(Example) When heat pump,three phase and
defrosting (normal) are set up, "20" is
displayed.
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns.)
8~39
17~30
This code is referred to check the unit's operating status.
Status of control
Code
Indoor unit
0
Normal
1
Hot adjustment
Defrosting
2
3
4
Heater ON
5
Anti-freezing
6
Over-rise prevention
7
Compressor OFF
1 : Cooling only
1 : For high humidity
Outdoor unit
Normal
Hot adjustment
Defrosting
Heater ON
Anti-freezing
Over-rise prevention
Compressor OFF
Unit
Code
display
:
:
:
:
:
: