Control modes
2-1. Frequency is restricted by the compressor electrical current (CT1).
2. Frequency
3-1. Voltage is corrected by bus voltage.
3. Voltage correction
3-2. Voltage correction by compressor's electric current (CT1). (PUHZ-RP4 to 6V only)
4. Power supply to
4-1. Compressor energizing method
locked compressor
ON
OFF
ON/OFF method
5. 52C
Frequency control such as Hz-down and no more Hz-up will be conducted
according to the compressor electrical current (CT1).
Models
PUHZ-RP1.6, 2, 2.5, 3VHA
PUHZ-RP4~6VHA
Inverter voltage will be corrected by dc bus voltage.
Even though the power supply voltage varies within i10%, the voltage should
be corrected in order to make the output voltage of inverter stable.
Output voltage of inverter is corrected by compressor's electric current (CT1).
Correction of
Models
starting current [A]
PUHZ-RP4~6VHA
• Compressor ON/OFF pattern when power is supplied;
1
4hrs
1hr
15 min.
Power supply
• Compressor ON/OFF pattern when power is cut off;
1
1hr
ON
OFF
30 min.
15 min. 15 min.
OFF
Comp. stopped
52C will turn ON/OFF in the following conditions.
• 52C turns ON when power is supplied, and remains ON regardless of the
compressor's ON/OFF.
• 52C turns OFF when power is cut off.
Control details
No more Hz-up
Hz-down
12.5 A
13 A
24.5A
26A
Correction of
max current [A]
16
24
1
1
W Repeated
1hr
1 Energized the outside
15 min.
15 min.
temperature is 15 or less
1
1
1
W Repeated
1hr
1hr
15 min.
60
Remarks
W Hz-down amount:
-5Hz per minute
"08" will be displayed
on the LED1 of "A-
Control Service Tool"
while power is
supplied to the
compressor.