Mitsubishi Electric PKA-RP1.6GAL Service Technical Manual page 105

Table of Contents

Advertisement

Indication
Outdoor controller board
LED1 (Green) LED2 (Red)
3 blinking 1 blinking
Abnormality of shell thermostat
and discharging temperature (TH4)
Abnormality of super heat due
to low discharge temperature
2 blinking
Abnormal high pressure (High
pressure switch 63H worked.)
4 blinking
Compressor over current breaking (Start-up locked)
Compressor over current breaking
Abnormality of current sensor (P.B.)
Abnormality of power module
Open/short of discharge thermistor (TH4)
5 blinking
Open/short of outdoor thermistors
(TH3, TH6, TH7 and TH8)
Open/short of outdoor ther-
mistor (TH8)
Abnormality of radiator panel
6 blinking
temperature
7 blinking
Abnormality of voltage
4 blinking
1 blinking
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor /Liquid (TH2)
Abnormality of pipe temperature
thermistor/Condenser-Evaporator
2 blinking
Abnormality of drain sensor (DS)
Indoor drain overflow protection
3 blinking
Freezing (cooling)/overheating
(heating) protection
4 blinking
Abnormality of pipe
temperature
W1 Error code displayed on remote controller
LED indications of fan operating condition (LED5 and LED6 on controller board)
Operation
LED5/LED6 (Red)
Normal (Stop)
Normal (Operating)
Operation LED5/LED6 (Red) Importance
2 blinks
6 blinks
Abnormal
7 blinks
is detected
8 blinks
Error
Contents
code
w1
1Check if stop valves are open.
U2
2Check if connectors (TH4, LEV-A, and LEV-B) on outdoor controller board are not
3Check if unit fills with specified amount of refrigerant.
U7
4Measure resistance values among terminals on indoor valve and outdoor linear
1Check if indoor/outdoor units have a short cycle on their air ducts.
U1
2Check if connector (63H) on outdoor controller board is not disconnected.
3Check if heat exchanger and filter is not dirty.
4Measure resistance values among terminals on linear expansion valve using a
1Check if stop valves are open.
UF
2Check looseness, disconnection, and converse connection of compressor wiring.
UP
3Measure resistance values among terminals on compressor using a tester.
4Check if outdoor unit has a short cycle on its air duct.
UH
U6
U3
1Check if connectors (TH3, TH4, TH6 and TH7) on outdoor controller board and conn-
U4
2Measure resistance value of outdoor thermistors.
1Check if indoor/outdoor units have a short cycle on their air ducts.
U5
2Measure resistance value of outdoor thermistor(TH8).
U9
1Check looseness, disconnection, and converse connection of compressor wiring.
2Measure resistance value among terminals on compressor using a tester.
3Check the continuity of contactor (52C).
4Check if power supply voltage decreases.
5Check the wiring of CN52C.
6Check the wiring of CNAF. (RP4~6VHA only)
P1
1Check if connectors (CN20, CN21 and CN29) on indoor controller board are not
P2
2Measure resistance value of indoor thermistors.
P9
P4
1Check if connector (CN31) on indoor controller board is not disconnected.
2Measure resistance value of indoor thermistors.
P5
3Measure resistance value among terminals on drain-up machine using a tester.
4Check if drain-up machine works.
5Check drain function.
P6
1Check if indoor unit has a short cycle on its air duct.
2Check if heat exchanger and filter is not dirty.
3Measure resistance value on indoor and outdoor fan motors.
4Check if the inside of refrigerant piping is not clogged.
P8
1Check if indoor thermistors (TH2 and TH5) are not disconnected from holder.
2Check if stop valve is open.
3Check converse connection of extension pipe. (on plural units connection)
4Check if indoor/outdoor connecting wire is connected correctly. (on plural units
W2 LED1 on power board for RP4, RP5 and RP6
1 blink: Power is supplied.
2 blinks: Power is supplied to compressor. Blinking: Limited control is being performed.
Fan stops.
Lit
Controller board is outputting waveform for fan driving.
Meaning of error code and detection method
Abnormality of bus voltage: Abnormal if bus voltage inspected for 1.5msec. is less than 60V or more than 390V.
1
Abnormality of overcurrent: Abnormal if current value of DC bus in fan controller board is over the cut-off point.
2
Abnormality of startup failure: Abnormal if the operating speed does not reach 100rpm even 12 sec passed after startup.
3
Abnormality of position detection: Abnormal if the position of U-phase cannot be detected after starting up fan.
4
Abnormality of disconnection: Abnormal if the first pattern of U/V/W-phase position detected after startup is H/H/H or L/L/L.
5
Error
Inspection method
disconnected.
expansion valve using a tester.
tester.
ector (CN3) on outdoor power board are not disconnected.
disconnected.
connection)
Contents
105
3 blinks: Power is supplied to warm up compressor.
Detailed
reference
page
P111
P112
P111
P113
P113
P113
P112
P112
P112
P112
P113
P106
P106
P108
P106
P107
P107
Remark
These
LEDs
are not
used
for
service.