9

CORRECTION FACTORS

9-1. INVERTER
9-1-1. COOLING CAPACITY CORRECTION FACTORS
Outdoor unit
5m (16ft)
PUY-A12/18
1.00
PUZ-A18
PUY-A24/30/36
1.00
PUZ-A24/30/36
PUY-A42
1.00
PUZ-A42
9-1-2. HEATING CAPACITY CORRECTION FACTORS
Outdoor unit
5m (16ft)
1.00
PUZ-A18
1.00
PUZ-A24/30/36
1.00
PUZ-A42
9-1-3. CAPACITY CORRECTION
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft)
100
95
90
85
80
75
70
5
10
<16>
<33>
Refrigerant piping length (one way)
10m (33ft)
0.985
0.988
0.985
Refrigerant piping length (one way)
10m (33ft)
0.997
0.997
0.997
15
20
25
<50>
<70>
<80>
<100>
Corrected pipe length
30m (100ft)
20m (70ft)
0.957
0.931
0.966
0.946
0.957
0.931
20m (70ft)
30m (100ft)
0.991
0.985
0.991
0.985
0.991
0.985
30
35
40
<115>
<130>
<150>
40m (130ft)
0.929
0.908
40m (130ft)
0.979
0.979
Cooling
Heating
Heating A18,24,30,36,42
models
(Up to 30m(100ft) for
A18 model)
Cooling A24,30,36 model
Cooling A12,18,42 models
(Up to 30m (100ft) for
A12/18 models)
45
50
m
<165>
ft
50m (165ft)
0.913
0.886
50m (165ft)
0.973
0.973
67