Troubleshooting for Outdoor Unit (25/35 class)

6.14 High Pressure Control in Cooling

F6
Remote
Controller
Display
Method of
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the
Malfunction
temperature being sensed by the heat exchanger thermistor exceeds the limit.
Detection
Malfunction
Activated when the temperature being sensed by the heat exchanger thermistor rises above
Decision
60˚C. (Deactivated when the said temperature drops below 50˚C.)
Conditions
Supposed
Causes
184
The installation space is not large enough.
Faulty outdoor unit fan
Faulty electronic expansion valve
Faulty defrost thermistor
Faulty outdoor unit PCB
Faulty stop valve
Dirty heat exchanger