Daikin Sky Air B-Series R-410A Service Manual page 259

Split system air conditioners
Table of Contents

Advertisement

FFQ25/35/50/60BV1B
Step
5
Reinstall the lead wire
of thermistor and anti
sweat tube on the
original position by
using two pieces of
heat resistance tie
wrap.
6
Put the heat exchanger
partition plate inside
and fix them with two
screws.
7
Pass the thermistor
ass'y through the
clamps and the slit of
partition plate securely
as the original state.
Pass the lead wire of
motor also through the
clamp securely.
8
Insert the grounding
terminal to the header.
248
Procedure
Anti sweat tube
Fan motor lead wire
Fan motor lead wire
Clamp
Slit of partition plate
∗ Heat resistance tie wrap
Parts No.:1278921
(Drg No.:4SA90202-1)
(S2673)
Heat exchanger
partition plate
(S2672)
Clamps
Thermistor ass'y
(S2683)
(S2684)
Si21-205
Points
Removal Procedure