than 15 meter due to length of the connection cable of remote air temperature sensor.
2. Height from floor is approximately 1.5 meter;
3. Remote air temperature sensor can not be located where the area may be hidden
When door is open;
4. Remote air temperature sensor can not be located where external thermal influence
may be applied;
5. Remote air temperature sensor should be installed where space heating is mainly
applied;
6. After the Remote air temperature sensor is installed,should be set the value form "0"
to"1" at the function code 1 in the control panel, so as to select remote air temperature
to the control point;
AIR-TO-WATER HEAT PUMP INSTALLATION MANUAL
30