17. Installation of Insulated Water Tank

17.1 Installation measure
The insulated water tank should be installed and keep levelly within 5m and vertically
within 3m from the Indoor unit. It can be installed in the room.
Standing water tank must be installed vertically with the bottom on the ground, never
suspended. Installation place must be firm enough and the water tank should be fixed on
the wall with bolts to avoid vibration, as shown in the following figure. Weight capacity of
water tank during installation should also be considered.
F i x
w i t h
b o l t s
The minimum clearance from the water tank to combustible surface must be 500mm.
There should be water pipe, hot water joint and floor drain near the water tank in favor of
water replenishment, hot water supply and drainage of water tank.
Connection of inlet/outlet waterway: Connect the safety check valve attached with the unit
(→ points at insulated water tank) with the water inlet of water tank with PPR pipe
according to the following figure, sealing with unsintered tape. The other end of the safety
check valve should connect with tap water joint. Connect the hot water pipe and water
outlet of water tank with PPR pipe.
Note: For safe use of water, water outlet/inlet of water tank must connect with a certain length
of PPR pipe ,L ≥70×R
( cm , R is inside radius of the pipe ) . Moreover, heat preservation should
W a t e r t a n k
2
AIR-TO-WATER HEAT PUMP INSTALLATION MANUAL
I n s t a l l e d o n t h e g r o u n d a n d
n e v e r s u s p e n d e d
Safety check valve
Tap water
35