Example:
If 16kw model is installed at a distance of 25m, (25-10)*50=750g refrigerant should be
added;
2.
Rated capacity is based on standard pipe length and maximum allowable length is base
on the product reliability in the operation;
3.
Oil trap should be installed every 5-7 meters when the location of outdoor unit is higher
than indoor unit.
AIR-TO-WATER HEAT PUMP INSTALLATION MANUAL