(2) Auto fan speed under cooling mode and fan mode
When Tamb.≥Tpreset + 2℃ , indoor fan operates at high fan speed;
When Tpreset < Tamb. < Tpreset + 2℃ , indoor fan operates at medium fan speed;
When Tamb.≤Tpreset, indoor fan operates at low fan speed;
(3) Auto fan speed under drying mode is defaulted at low fan speed.
Note: 1.Under auto fan speed, during switchover between high speed and medium speed, medium speed and low speed, and high
speed and low speed, there should at least 3min and 30s operation time.
2.Fan speed "high", "medium", and "low" is corresponding to "fan speed 5", "fan speed 3" and "fan speed 1".
4. Sleep
Sleep mode is only valid under cooling mode and heating mode;
Cooling mode: Basing on the set temperature of remote controller, after turning on the sleep function for a few hours, set temperature
will increase properly and automatically according to human body's comfort.
Heating mode: Basing on the set temperature of remote controller, after turning on the sleep function for a few hours, set temperature
will decrease properly and automatically according to human body's comfort.
5. Timer function
Controller is with general timer function and clock timer function simultaneously. When you selecting the remote controller with general
timer, you can only activate the general timer function of controller; when you selecting the remote controller with clock timer, you can
only activate the clock timer function of controller.
(1) General timer
Timer precision for general timer is 0.5hour, and 24hours circulating timer can't be set.
◆ Timer ON can be set at unit OFF. If selected ON time is reached, the system will start to operate according to previous setting
status by remote controller. Time setting range is 0.5-24hr in 30-minute increments.
◆ Timer OFF can be set at unit ON. If selected OFF time is reached, the unit will stop operation. Time setting range is 0.5-24hr in
30-minute increments.
(2) Clock timer
Timer precision for clock timer is 1min, and 24hours circulating timer can be set.
◆ Timer ON: If timer ON is set during operation of the unit, the unit will continue to operate. If timer ON is set at unit OFF, upon ON
time reaches the unit will start to operate according to previous setting status by remote controller.
◆ Timer OFF: If timer OFF is set at unit OFF, the system will keep OFF status. If timer OFF is set at unit ON, upon OFF time reaches
the unit will stop operation.
◆ Timer change
Under timer status of system, you can set timer ON and timer OFF by pressing ON/OFF button on remote controller. You can also set
timer setting again and the system will operate according to the last setting status.
If timer ON and timer OFF are set at the same time during operation of the unit, the unit will keep operating at current status till OFF
time reaches. When ON time reaches, the unit will be turned on automatically. The unit will circulate like that every 24hours.
If timer ON and timer OFF are set at the same time at OFF status, the unit will OFF status till ON time reaches. When OFF time
reaches, the unit will be turned off automatically. The unit will circulate like that every 24hours.
6. Memory function
(1) Memory when power failure upon turning on the unit
◆ Memory content: ON status, mode, up&down swing, light, set temperature, set fan speed, general timer, Fahrenheit/ Centigrade,
◆ General timer can be memorized. Timer will be recalculated from the time of energization.
◆ Clock timer can't be memorized.
(2) Memory when power failure upon turning off the unit
◆ Memory content: ON status, mode, up&down swing, light, set temperature, set fan speed, general timer, Fahrenheit/ Centigrade
◆ General timer can be memorized. Timer will be recalculated from the time of energization.
◆ Clock timer can't be memorized.
7. Health function
During operation of the indoor fan, press health button on the remote controller to start health function (If there is not health button on
the remote controller, the unit defaults health function ON).
When the fan stops operation or press health button on remote controller again, health function will be turned off.
8. I FEEL function
When I FEEL command is received, the controller will operate according to the ambient temperature sent by the remote controller
(For defrosting and cold blow prevention, the unit operates according to the ambient temperature sensed by the air conditioner). The
remote controller will regularly send ambient temperature data to the controller. When the data has not been received for a long time,
the controller will operate according to the temperature sensed by the air conditioner. If I FEEL function hasn't been started up, the
ambient temperature will be that sensed by the air conditioner.