9 OPERATION RANGE

Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of
the rated voltage.
Power Supply
MODEL
CU-
V50BBP8
W50BBP8
Indoor and Outdoor Temperature
• • • • Cooling only type
Model 50Hz CU-V50BBP8
Operating
Cooling
• • • • Heat pump type
Model 50Hz CU-W50BBP8
Operating
Cooling
Heating
Unit Main Power
Phase, Volts
3N~380
3N~400
3N~415
Hz
Indoor Temp. (D.B./W.B.) (°C)
Max
50
32/23
Hz
Indoor Temp. (D.B./W.B.) (°C)
Max
50
32/23
50
27/-
Hz
Max
50
418
50
440
50
457
Min
21/15
Min
21/15
16/-
28
Applicable Voltage
Min
342
360
374
Outdoor Temp. (D.B./W.B.) (°C)
Max
Min
43/-
-5/-
Outdoor Temp. (D.B./W.B.) (°C)
Max
Min
43/-
-5/-
24/18
-10/-