NOTE: If the remote control display setting temperature (To) is 29°C or higher, the heating thermostat turns
on when the room temperature is 31°C.
2. Thermostat characteristics during dry mode.
During dry mode operation, cooling mode operation is carried out in accordance with the indoor temperature as shown in the
table below.
* When modes (2) and (3) are active, dry mode operation starts when the cooling thermostat turns on.
When modes (2) and (3) have been stopped, the 10 min./5 min. times have no relevance. However, if the indoor temperature
is less than or equal to the remote control unit setting temperature, mode (4) is forcibly activated.
3. Thermostat characteristics during automatic changeover operation
a. Settings at the start of automatic changeover operation
When operation changes from other modes to automatic changeover mode, operation starts at the temperature
characteristics given in the table below.
b. Thermostat characteristic when switching between cooling and heating mode operation
Switching between cooling mode and heating mode operation is carried out as shown in the table below.
However, during automatic changeover operation, the operation will not change within 10 minutes after the thermostat has
switched off, either cooling mode or heating mode.
(The 10 minutes timer will be cancelled when operation is changed to other modes (manually) or when operation stops and
the thermostat turns on.)