CS-F24DB4E5 CU-L24DBE5 / CS-F28DB4E5 CU-L28DBE5
1.4.
Operation range
1.4.1.
Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of
the rated voltage.
MODEL
CU-
L24DBE5
L28DBE5
1.4.2.
Indoor and Outdoor Temperature
• • • • Model 50Hz CU-L24DBE5, CU-L28DBE5
Operating
Cooling
Heating
Unit Main Power
Phase, Volts
1~240
1~220
1~230
Hz
Indoor Temp. (D.B./W.B.) (°C)
Max
50
32/23
50
27/-
Hz
50
50
50
Min
21/15
16/-
4
Applicable Voltage
Max
Min
264
216
242
198
253
207
Outdoor Temp. (D.B./W.B.) (°C)
Max
Min
43/-
-15/-
24/18
-20/-