6.35 Address 47 - Default EEPROM
CAUTION:
Entering a [1] in Address 47 will erase all
prior programming.
6.36 Address 48 - Automatic Test Report
Interval
Page 20
Copyright © 2001 Detection Systems, Inc.
6.37 Address 49 - Hours to First Auto Test
Report
• Set this value to the number of hours from the time the
panel was powered up for the first report. Example: If
the panel was powered up at 2 PM and you want test
reports at 3 AM, set to [0 1 3] (2 PM + 13 hours = 3
AM). If not set, the first report will be sent 12 hours
after panel power up.
6.38 Address 50 - AC Failure Report Delay
• Address 32 must be programmed to this report.
NOTE: If AC power should restore before the "AC
Failure Report" time, no AC Failure Report will
be sent.