6.5 Address 05 - Zone Response Time
All six zones can be programmed to respond at either 300
ms (±100 ms) or a programmable time (common to all
zones, the time is programmed into Address 06) that can
be configured to be between 160 ms and 2.5 seconds.
6.6 Address 06 - Programmed Zone Response
Time
Sets the time value used in Address 05.
DS7060-AUS Reference Guide
Copyright © 2001 Detection Systems, Inc.
6.7 Address 07 - Zone Restoral Options
• Restore when Sounders Silence: If programmed, a
zone sends a restoral report and is ready to activate
again only after the burglary bell cutoff time expires or
the bells are silenced. The zone can alarm multiple
times per armed period.
• Restore with Zone: If programmed, a zone sends a
restoral report and is ready to activate again as soon as
it physically restores. The zone can alarm multiple
times per armed period.
• Restore when Disarmed (or Reset): If the zone
returns to normal before the bell timer elapses, the
alarm display will continue and no restoral will be
reported. When the bell timer then elapses, whether or
not the zone has restored, the bell will shut down (if
selected) but the alarm display will continue and no
restoral will be reported. When the system is disarmed
(or reset) the bell will silence, the displays will clear and
restoral will be reported along with the open/reset event
(if programmed). If the zone is a 24 hour zone and has
not restored to normal, will not report zone restoral until
the zone restores. Unrestored 24 hour zones will show
as "not ready" and will prevent the system from arming.
In this case, the system will reinitiate the sounders and
displays for those zones, but will not send any fire
alarm transmission to the central station for those
zones, unless a previous restoral has been sent. Fire
zones always restore when the system is reset,
regardless of this selection.
Page 9