6.0 Programming the DS7060
6.1 Address 01 - Zone Programming
A zone is an input to the DS7060 Control Communicator.
There are 6 hard-wired zones on the main circuit board.
• Disabled: These zones are not monitored, and will not
generate alarm or trouble conditions.
• Perimeter Instant: These zones arm and disarm with
the panel, and never have entry or exit delays. Violation
of this type of zone will cause an intrusion alarm.
• 24-Hour Auxiliary: This zone type will cause an
auxiliary alarm. It is always active. An alarm on a 24-
hour zone (fire or aux.) will be silenced by entering a
disarm code whether the control is armed or not. If the
24-hour zone restores and alarms again the alarm will
sound again. 24-hour zones may generate trouble
conditions during armed or disarmed periods. All 24-
hour zones that have alarmed and are not restored will
show as "Not Ready." They will prevent arming unless
the panel is force armed. 24-hour zones that have been
bypassed manually will remain so until manually
unbypassed, even if the control is armed and disarmed.
Bypasses of these zones will be displayed on the
keypad.
Page 6
Copyright © 2001 Detection Systems, Inc.
Perimeter Delayed: These zones have entry or exit
delays unless the panel is armed in the "No Entry"
mode. In the "No Entry" mode, the exit delay is in effect
immediately after entering the "No Entry" mode, but is
disabled upon expiration of the exit delay.
A delayed zone is ignored during the programmed times
immediately following arming during the exit delay. If
the zone is faulted while the control is armed and not in
exit delay then an entry delay cycle will be started, and
a continuous entry tone will be sounded at the keypads.
If the control is not disarmed by the end of the entry
delay, an alarm will result. There are no keypad tones
during the exit delay unless the feature "Keypad Audible
During Exit Delay" is selected. Refer to Section 6.9,
Address 09. If an entry delay is running and another
entry delay zone is faulted, the entry delay timer is
unaffected and will continue timing from the first entry.
The entry delay time and exit delay time can be set
independently.
If a delayed zone remains faulted at the end of an exit
delay, the panel will optionally signal an exit error
condition. The entry delay will be begin as above, and
the alarm output will activate with the pattern selected
for that zone. If the control is not disarmed by the end of
the entry delay, an alarm will result, and an exit error
report will be sent to the central station (following the
alarm report if programmed). The alarm output will
deactivate. If the control is disarmed during the delay
period started by the exit error condition, no reports will
be sent to the central station and any outputs on during
the exit error will deactivate. The exit error report does
not follow the dialer delay option.
• Interior Follower: This zone is not active when the
panel is disarmed, or is armed in the perimeter only
mode. When the zone is active, if a delayed zone is
violated first, this zone is also delayed. If an instant
zone or this zone type is violated first, this zone is not
delayed. This zone is not active during the exit delay.
• Interior Home/Away: This zone becomes interior
instant if the system is armed and an entry/exit delay
zone is violated during the exit delay time. If the system
is armed and an entry/exit zone is not violated, these
zones will be bypassed. These zones are bypassed if
armed perimeter only.
• Interior Instant: These zones arm and disarm with the
panel. They are not active if the panel is armed in the
"perimeter only" mode. They never have entry or exit
delays. Violation of this type of zone will cause an
intrusion alarm.
• Perimeter Homeguard: This zone type is active when
the panel is armed. When the panel is armed perimeter
only, this is a delayed zone. When armed full, this is an
instant zone.
• Perimeter Follower Homeguard: These zones are
always delayed when the panel is armed in the
perimeter only mode. When the panel is fully armed,
these zones are delayed if a delayed zone is violated
DS7060-AUS Reference Guide