C. Vent Minimum Clearances
D
E
B
L
FP
= FIREPLACE OPENING
A
= 24 in. . . . . . . . . . clearances above grade,
B
= 12 in. . . . . . . . . . clearances to window or door
20 in. . . . . . . . . . vinyl windows or siding.
D
= 50 in. . . . . . . . . . vertical clearance to unventi-
60 in. . . . . . . . . . vinyl clad soffits.
F
=
9 in. . . . . . . . . . clearance to outside corner.
G*
=
7 in. . . . . . . . . . clearance to inside corner,
H
=
3 ft. (Canada) . not to be installed above a gas
I
=
3 ft. (USA)
6 ft. (Canada) . clearance to service regulator
*
48 in. minimum for vinyl windows or vinyl siding.
**
only permitted if veranda, porch, deck or balcony is fully open
on a minimum of 2 sides beneath the floor, or if the screened
porch guidelines are followed.
Note 1: Local codes or regulations may require different clearances.
Note 2: Appliance in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1) There must
be a 3 ft minimum between terminations or between the
fireplace and termination. 2) All mechanical air intakes within 10
ft of a termination must be a minimum of 3 ft below the fireplace
hood. 3) All gravity air intakes within 3 ft of the fireplace opening
must be a minimum of 1 ft below the termination.
Figure 3.5 Minimum Clearances
12
Outdoor Lifestyles by Hearth & Home Technologies • Palazzo Installation Manual • 4082-311 Rev. A • 06/08/15
B
FP
FP
F
FP
X
= AIR SUPP LY INLET
veranda, porch, deck or
balcony.
that may be opened, or to
permanently closed window.
lated soffit or to ventilated soffit
located above the terminal.
non-vinyl siding.
meter/regulator assembly within
3 ft (914 mm) horizontally from
the center line of the regulator.
vent outlet and electric service.
G
FP
A
H
B
= AREA WHERE FIREPLACE IS NOT PERMITTED
J
=
9 in. (USA)
12 in. (Canada) . clearance to non-mechanical air
K
=
3 ft. (USA)
6 ft. (Canada) . clearance to a mechanical air
L
=
. . . . . . . . . . (See note 4)
M** = 50 in. . . . . . . . . . clearance under veranda, porch,
Not allowed: . . . . . . vinyl
N*
= 14 in. . . . . . . . . . clearance to inside corner,
O
= 50 in.
P
= 88 in.
Palazzo
___________________________________________________________________________
1 additional termination cap
___________________________________________________________________________
2 additional termination caps Q + 6 feet
___________________________________________________________________________
3 additional termination caps Q + 9 feet
R
MAX
This fireplace is approved for installation onto screen porches with the
following guidelines:
Minimum porch area: 96 sq ft
Minimum ceiling height: 88 in.
Minimum of two walls must be screened
Minimum top of screen height, side walls: 80 in.
Minimum screen area: 64 sq ft
Note 3: There may be some odor and small amounts of soot associated
with burning outdoor gas fireplaces on a screened porch. Consider
prevailing wind direction for best flame performance.
Note 4: For appliances installed facing or opening onto public property or
property servicing more than one single family dwelling, such as
driveways, sidewalks, etc. refer to local building codes/regulations for
proper clearances.
O
P
R
FP
Q
(See Note 2)
Alcove
M
I
FP
X
J or K
supply inlet to building or the
combustion air inlet to any other
appliance.
supply inlet.
deck, balcony or overhang.
non-vinyl siding. (Alcove)
Q
R
MIN
10 feet
2 x Q
Q + 3 feet
1 x Q
2/3 x Q
1/2 x Q
= (2 / # caps plus fireplace ) x Q
ACTUAL
N
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL