Combustion Air System and Exhaust System
Length of the combustion air inlet and exhaust lines in total:
With muffler:
Without muffler:
NOTE:
If the exhaust line is over 2 m in length the lines must be insulated
(to prevent falling below the dewpoint)
Internal diameter of the lines:
Combustion air line:
exhaust line (metal):
Minimum bending radius:
Total bends:
Combustion air line:
Exhaust line:
IMPORTANT!
If the exhaust pipe ends other than as shown in Figure 22, it will pose a fire risk.
7.1

Exhaust Muffler

Webasto recommends installing an exhaust silencer to reduce noise. The installation must satisfy the following
requirements:
- The installation location is as close as possible to the heater.
Installing exhaust muffler:
- Ensure the correct installation position.
- Do not secure the exhaust muffler to heat-sensitive parts (e.g. brake lines, electrical cables).
- Maintain adequate distance from heat-sensitive parts. A heat shield can be fitted.
- Install exhaust muffler such that condensation can drain off through the condensation drain hole in the exhaust
muffler.
Figure 23. Exhaust muffler - exhaust flow is non-directional (arbitrary)
Webasto Thermo & Comfort N.A., Inc.
max. 2.0 m
max. 5.0 m
25 mm
24 mm
50 mm
max. 270°
max. 270°.
22
Air Top Evo 40/55
The exhaust pipe must be securely attached no further
than 150 mm (6 in.) from the end of the exhaust pipe
to ensure that the angle of 90° ± 10° is maintained.
Installation position
10°
Discharge direction almost vertical 90° ± 10°
Figure 22. Exhaust pipe opening