8. CONTROL MODE SETTING

8-1 Control mode selection

APxG5 provides 5 different control modes :
1. v/f open loop control.
2. v/f close loop control with PG (pulse generator).
3. v/f sensorless close loop control.
4. Current vector with PG close loop control.
5. Sensorless current vector control.
The performance depends on the application by using key-
pad.
V/F open loop control mode is a factory setting.(F23=2)
Please follow the flow chart below to set control mode and
input motor parameter.
Open loop
Speed Feedback F13 = 1
PG (Pulse/rev) F14 =(Pulse)
Control Mode
Control Mode
F23 = 2
Note : It needs to key in the motor parameters while setting F23=4,
5,6. If the motor parameters are unknown, please follow the
"Auto Turning Procedure" to set up these parameters.
Control Mode Setting Procedure
Nameplate of motor parameter
( F0 ~ F5 )
Nameplate of inverter parameter
( F16 )
V / F Control
Control
Mode
Loop
Close loop
With
PG
NO
YES
Control Mode
F23 = 3
F23 = 4
Operating
Vector Control
With
PG
YES
Speed Feedback F13 = 1
PG (Pulse/rev) F14 =(Pulse)
Control Mode F23 = 0
Execute Auto tunning
Control Mode
F23 = 5
24
NO
Control Mode F23 = 0
Execute Auto tunning
Control Mode
F23 = 6