Application - REMEHA 350 Technical Information

Atmospheric gas boiler with reduced nox emission 64 - 174 kw
Hide thumbs Also See for 350:

Advertisement

4. APPLICATION

4.1 L.P.H.W. system
4.1.1 Water temperature
Maximum water temperature is 110°C (high limit
thermostat).
Highest boiler water temperature is 95°C (control
thermostat).
Minimum return water temperature is 20°C at a fl owrate
related to a t of 20°C (fl ow/return temperature).
4.1.2 Water pressure
Boiler sections pressure test at 10 bar.
Maximum pressure test boiler block is 8 bar.
Maximum working pressure is 6 bar.
Minimum working pressure boiler is 0.8 bar.
Optional a water pressure switch set at 0.8 bar can be
supplied with the boiler.
4.1.3 Water fl ow
The minimum water fl ow through the boiler is:
Output boiler in kW = ... m
93
This minimum fl ow must be maintained for 5 minutes after
the burners stops fi ring to avoid high temperature shut-
down due to residuel heat gain.
Due to the design and manufacture of the boiler no specifi c
minimum water fl ow requirement exists other than high-
temperature protection.
3
/h
4.1.4 Water treatment
Water treatment under normal circumstances is not
necessary (see our water quality recommendations).
4.1.5 Noise level
The noise level measured around the boiler depending
on boiler room construction is about 50 dBA.
(Noise level taken at 1 meter from the boiler).
4.2 Chimneys
The average fl ue gas temperature is so low that the
chimney must be in accordance with the guidelines of
British Gas and BS 6644.
5