Harman Accentra 52i Installation Manual
Hide thumbs Also See for Accentra 52i:

Advertisement

Accentra 52i Pellet Insert Zero Clearance Cabinet
Part #1-00-574323
Accentra 52i Pellet Insert ZC Cabinet
Accentra 52i Pellet Insert Mounting Frame
Accentra 52i Pellet Insert
www.harmanstoves.com
R:\Todd\Instruction Sheets_3-89-574323_RevF

Advertisement

loading

Summary of Contents for Harman Accentra 52i

  • Page 1 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 Accentra 52i Pellet Insert ZC Cabinet Accentra 52i Pellet Insert Mounting Frame Accentra 52i Pellet Insert www.harmanstoves.com R:\Todd\Instruction Sheets_3-89-574323_RevF...
  • Page 2 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 Contents of Kit; Cabinet components- 1- Top Panel 1- Bottom Panel 2- Side Panels 1- Rear Panel 32- #10 X 3/4” Tek Screws (Self-Tapping) 1/4-20 x 5/8 4- 1/4-20 x 5/8 Thread Cutters Thread Cutters Tools Needed;...
  • Page 3 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 NOTE: When Fiberglass insulation is placed directly on top of the ZC Cabinet it should not touch the pipe. The outer ring knockout of the flue pipe opening is designed to install a standard 6” sheetmetal starter collar and a short length of pipe to keep the insulation from touching the vent pipe.
  • Page 4 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 The finished face of the fireplace facade “MUST” be flush with the ZC Cabinet front face when completed. The flanges ARE NOT designed to support the weight of the cabinet NOTE: See the following pages and the Accentra Insert. They are only to secure cabinet to the wall for rough-in instructions for other framing. Adequate framing under the hearth and ZC cabinet MUST facing materials.
  • Page 5 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 Caution should be taken NOT TO HAVE a stud within 5” of the center line of the flue pipe. (Use PL Vent Pipe ONLY) This should allow room for any PL Vent certified wall pass through. NOTE: When fiberglass insulation is placed directly on top of the ZC Cabinet it should not touch the vent pipe. The outer ring knock out of the flue pipe opening is designed to install a standard 6”...
  • Page 6 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 29-9/16” rough opening Minimum Minimum depth 16-7/8”...
  • Page 7 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 Flue Pipe Rough-in Support Kit #1-00-574246 Harman® Vent Pipe Stub for 3” PL Vent Pipe #1-00-674039 Harman® Vent Pipe Stub for 4” PL Vent Pipe #1-00-574034 Drill #10x3/4 Tek Screws Precut Alignment Hole...
  • Page 8 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 Mounting holes flue Mounting holes for outside air rough-in-support brackets. rough-in-support brackets. Accin 52i Mounting Frame There are 4 holes located in the bottom of the There are 4 cabinet mounting holes in...
  • Page 9 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 Combustible materials are allowed to touch the outside of the ZC Cabinet. Minimum Flue Configuration. 3” or 4” PL Vent Pipe 12” PL Vent manufactures wall pass-through. NOTE: When fiberglass insulation is placed directly on top of the ZC Cabinet it should not touch Clearance to shrubbery, grass, the vent pipe. The outer ring knockout of the flue or any other type plant pipe opening is designed to install a standard 6”...
  • Page 10 Accentra 52i Pellet Insert Zero Clearance Cabinet Part #1-00-574323 Venting clearances for in room installation of the Zero Clearance Cabinet. 12" MIN. Storm Collar NOTE: • Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY. • Illustrations/diagrams are not drawn to scale. Flashing • Actual installation may vary due to individual design. NOTE: 3" MIN. In Canada, where passage through a wall or partition of combustible construction 3" MIN. is desired, the installation shall conform to CAN/CSA-B365. 3" MIN. PL Vent manufacturer’s firestop space and support No insullation or other combustible materials are allowed within 3”...