Air/flue gas routing
Single boiler system:
Implementation versions, condensing boiler
B23
Flue in a duct and combustion air directly via the boiler (open flue)
Connection to a moisture-resistant flue gas chimney with horizontal
B33
connection line
Combustion air supply and flue gas routing via the roof in a common
C33
pressure range
Vertical concentric roof outlet through a pitched or flat roof, vertical
C33
concentric air/flue gas routing for installation in a duct (balanced
flue)
Connection to a moisture-resistant balanced flue chimney (balanced
C43
flue)
Terminals of the combustion air and flue are in different pressure
C53
ranges (balanced flue)
Connection to flue on an external wall with horizontal eccentric
C53
connection line (length 2.5 m) (balanced flue)
The flue gas system has not been tested and certified with the appliance.
C63
It must meet the building requirements of the relevant country.
Connection to a moisture-resistant chimney and combustion air
C83
through an external wall (balanced flue)
Vertical flue for installation in a duct with horizontal eccentric
connection line, balanced flue ventilation air supply DN200. The
C93
terminals are in the same pressure range, combustion air supply via
existing duct (edge length in mm)
* Applies to horizontal connection line DN 200 with length of 2 m and an 87° bend (corresponds to 3 m effective length)
Comments:
Length of connection line: 2 m, 1 additional 87° bend (corresponds to 3 m effective length)
Duct cross-section = minimum annular gap to DIN 18160 Part 1
Available fan draught: MGK-2: 10 - 150 Pa
(maximum length corresponds to the total length from the appliance to the flue terminal)
Note:
Systems C33 and C83 are also suitable for installation in garages.
Where necessary, adapt the installation examples to the relevant Building Regulations and requirements in your country/region.
Discuss any questions relating to the installation of inspection covers and ventilation air supplies with your local flue gas
inspector.
The length dimensions refer to concentric balanced flue systems and flues, specifically only to original Wolf components.
The following balanced flues or flues with CE-0036-CPD-9169003 certification may be used:
-
Flue DN 160, DN 200, DN 250 and DN 315
-
Concentric balanced flue DN 250/350 and DN 315/400
The necessary identification labels are supplied with the Wolf accessory concerned.
Please also observe the installation information supplied with the accessories.
3063772_201507
17. Air/flue gas routing
Maximum length in metres,
MGK-2
390
470
DN160 *
8
-
DN200
50
40
DN 250
50
50
DN250
Calculation to EN 13384
DN315
(balanced flue manufacturer)
DN250
Calculation to EN 13384
DN315
(balanced flue manufacturer)
DN250/350
38
27
DN315/400
47
38
DN250
Calculation to EN 13384
DN315
(balanced flue manufacturer)
DN200
35
22
DN250
50
50
DN200/300
39
24
DN250/350
50
50
DN315/400
-
-
DN250
Calculation to EN 13384
DN315
(balanced flue manufacturer)
DN250
Calculation to EN 13384
DN315
(balanced flue manufacturer)
DN250/250
50
45
370x370
DN250/315
-
50
450x450
DN315/315
-
-
450x450
vertical
550
630
-
-
19
9
50
50
13
4
22
13
-
-
50
24
-
-
50
34
-
50
16
-
50
23
-
33
25