Fault
Fault
code
26
Fan speed >
30
CRC burner control unit
32
Fault in 23 V AC supply
35
BBC missing
36
BCC faulty
37
Incorrect BCC
38
BCC update required
39
BCC system error
41
Flow monitoring
42
Condensate pump is not
pumping anything out
44
Flue gas pressure switch
52
Max. cylinder heating time
53
IO control deviatn
60
Siphon backpressure
78
Header sensor fault
90
BCU comm error
95
Prog. mode
96
Reset
98
Flame amplifier
99
Burner control unit
system fault
3063772_201507
35. Troubleshooting
Cause
The fan does not stop
The EEPROM record is invalid
23 V AC supply outside the permissible
range (e.g. short circuit)
Boiler chip card has been removed or not
correctly inserted
Faulty boiler chip card
The boiler chip card is incompatible with the
control PCB
Boiler chip card fault, PCB requires a new
boiler chip card (replacement)
Faulty boiler chip card
Return temperature > flow temperature
Faulty condensate pump, drain line blocked,
no power supply to pump
Flue system back pressure too high
Cylinder heating takes longer than permitted
Wind recognition, severe storm, insufficient
ionisation signal during operation, burner
contaminated
Siphon or flue system is blocked
Faulty sensor or lead
Emergency stop via ChipCom, faulty
communication between control PCB and
burner control unit
Burner control unit is controlled by PC
Reset button pressed too often
Internal burner control unit fault Monitoring
electrode short circuit
Internal burner control unit fault
Remedy
Test the fan's PWM and power
cable, test fan, press reset, test flue
system for strong draught
Switch the power supply OFF and
ON. If unsuccessful, replace the
burner control unit.
Switch the power supply OFF and
ON. If unsuccessful, replace the
control PCB.
Refit the correct boiler chip card
Replace boiler chip card
Refit the correct boiler chip card
Reinsert boiler chip card, replace
boiler chip card
Replace boiler chip card
Vent system, check heating circuit
pump, test flow and return pipe
connection
Check pump, check drain line,
check mains plug and fuse
Heat exchanger contaminated,
check flue system, test flue gas
damper, press reset
Test DHW sensor (cylinder sensor)
and sensor lead, press reset
Test monitoring electrode, check
flue system, press reset, clean
burner
Clean siphon; test flue system,
ventilation air, gas supply pressure
(flow pressure) and monitoring
electrode
Check sensor and lead; replace if
required
Switch the power supply OFF
and ON. If unsuccessful, call in a
specialist contractor.
No action
Switch the power supply OFF
and ON. If unsuccessful, call in a
specialist contractor
Press the reset button, and switch
the power supply OFF and ON. If
unsuccessful, call in a specialist
contractor, test monitoring electrode
Switch the power supply OFF
and ON. If unsuccessful, call in a
specialist contractor.
63