Section 6: Power Supply Requirements

6.1 Overview

This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1.
Calculating the total amount of AC branch circuit current required to operate the system
2.
Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3.
Calculating the size of batteries required to support the system if an AC power loss occurs
4.
Selecting the proper batteries for your system

6.2 Calculating the AC Branch Circuit

The power supply requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,
from the power source to the power supply. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm
wire with 600 volt insulation for this branch circuit.
Use Table 6.1 to determine the total amount of current, in AC amperes, that must be supplied to the
system.
Device Type
HPF24S6/8(C)
HPF24S6/8E
38
Number of
Devices
or
1
[
]
[
]
[
]
[
]
Sum Column for AC Branch Current Required
Table 6.1 120/240 VAC Branch Circuit Requirements
Current Draw
(AC amps)
3.2
x
or
1.6
x
[
]
x
[
]
HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011