Connect The Drain Pipe - Carrier 40MB*C Installation Instructions Manual

Cassette ductless split system system sizes 09"" 18 air conditioner
Hide thumbs Also See for 40MB*C:
Table of Contents

Advertisement

2) Be sure to insulate
both the gas and liquid
piping.
Use
separate
thermaJ insuJation
pipes for gas and liquid
refrigerant
pipes. See the figure
below.
Inter-unitwire
4
CONNECT THE DRAIN PIPE
4.1
Installation
of drain piping
Install the drain piping as shown in the figure below and take
measures against condensation.
Improperly
rigged piping could
lead to leaks and eventually
wet furniture and belongings.
Gas pipe
Liquid pipe
//b'//b'////._///._b'/._b'b'b'._///._///////H///NH
Liquid pipe
_
-- 1
Gas pipe
insulation
/
Drain hose
|
--
2
Finishing tape
_
3) Finally, insulate
as shown
in the figure
below.
6
5
3
I
2
4
I
Liquidpipe
2
Gaspipe
3
Insulationfor liquidpipe fitting
4
Insulationfor gas pipe fitting
5
Clamps
(use2 clamps per insulation)
6
Indoorunit
Piping insulation
procedure
I
6
3
2
6
4
5
I
63
2
6
4
5
A
c
S
I '
I
'F"
A
C
B
I
Piping insulationmateria!(fieldsupply)
2
Flare nut connection
3
Insulationfor fitting (field supply)
4
Piping insulationmaterial (main unit)
5
Indoor unit
6
Clamp (field supply)
A
Turn seamsup
B
Attach to base
C
Tightenthe part other than the piping insulationmaterial
A
For local insulation,
be sure to insulate local piping
all the way into the pipe connections
inside the unit.
Exposed piping may cause condensation
or may
cause burns when touched.
Make sure that no oil remains on plastic parts of the
decoration panel (optional equipment).
Oil may cause degradation
and damage to plastic
parts.
4.2
HIHIIHIHIHIIHIHIHIIHIHIHIIHIHIHII_
I
Hangingbar
2
I/I00 gradient
install the drain pipes,
Keep piping as short as possible and slope it downwards
at a
gradient of at least 1/100 so that air may not remain trapped
inside the pipe.
Keep pipe size equal to or greater than that of the connecting
pipe (PVC pipe, nominal diameter
0.8in/2Omm in, outside
diameter
1in/25mm).
Push the drain hose as far as possible over the drain socket,
and tighten the metal clamp securely.
I
Drain socket (attached to the unit)
2
metal clamp
3
Drain hose
4
Insulation (field supply)
Insulate the drain hose inside the building.
If the drain hose cannot be sufficiently
set on a slope, fit the
hose with drain raising piping (field supply).
Make sure that heat insulation
work is executed
on the
following 2 spots to prevent any possible water leakage due
to dew condensation.
1 Indoordrain
pipe.
2
Drain socket.
14