Electric Wiring Work - Carrier 40MB*C Installation Instructions Manual

Cassette ductless split system system sizes 09"" 18 air conditioner
Hide thumbs Also See for 40MB*C:
Table of Contents

Advertisement

4.4 Testing of drain piping
4.3
How to perform
piping
///////////////////////////i
'_-
1
2
I
2
3
4
5
6
Ceilingslab
Hanger bracket
Adjustable range
Drain raisingpipe
Drain hose
Metal clamp
Unit: mm
Connect the drain hose to the drain raising pipes, and
insulate them.
Connect the drain hose to the drain outlet on the indoor unit,
and tighten it with the clamp.
Precautions
Install the drain raising pipes at a height of less than
20.9 in/530 mm.
Install the drain raising pipes at a right angle to the indoor
m
unit and no more than 11.8 in/300 mm from the unit.
To prevent air bubbles, install the drain hose level or slightly
tilted up (_<3 in/75 mm).
The incline of drain hose should be 3 in/75 mm or less so
that the drain socket does not have to withstand
additional force.
To ensure a downward slope of 1:100, install hanging
bars every 3.3ft/1 m to 4.9ft / 1.5 m.
[]
When unifying multiple drain pipes, install the pipes as
shown in figure below. Select converging
drain pipes whose
gauge is suitable for the operating
capacity of the unit.
[]
rq--rr7
6
1
°If
- _-_-_-_
.................
1
Unit: mm
T-jointconverging drainpipes
Drain piping connections
Do not connect the drain piping directly to sewage
pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain
pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of
drain pipe blockage if water collects in the drain pipe.
After the piping work is finished,
check if drainage flows smoothy.
Add approximately
1L of water gradually
through the air discharge
outlet.
Method of adding water (see the figure below)
4.2in/106
Freshair intake (2.6in/65)
I
2
1
2
Unit: in/mm
Plasticwatering can(tube should be about 3.9in/I00 mm long)
Water-receiver
,,,
When electric wiring work is finished,
check drainage flow during
COOL running, explained in "Test operation" on page 16.
5
ELECTRIC WIRING WORK
General instructions
All field wiring and components
must be installed by a licensed
electrician
and must comply with relevant
regulations.
[]
Use copper wire only.
[]
Follow the 'Wiring diagram'
attached to the unit body to wire the
outdoor unit, indoor units and the remote controller.
A circuit breaker capable of shutting down power supply to the
entire system must be installed.
Note that the operation will restart automatically
if the main
power supply is turned off and then turned back on again.
[]
Be sure to ground the air conditioner.
Do not connect the ground wire to gas pipes, water pipes,
lightning rods, or telephone ground wires.
Gas pipes: might cause explosions
or fire if gas leaks.
Water pipes: no grounding
effect if hard vinyl piping is used.
Telephone ground wires or lightning rods: might cause
abnormally
highelectric
potential in the ground during
lightning storms.
The specification
of power
Model
Phase
9K~18K
1Phase
Power
Frequency and volt
208-230V
Circuit breaker/Fuse(A)
20/16
15