Connect Condensate Drain; Install Flue Hood - Carrier 48SD Installation Instructions Manual

Table of Contents

Advertisement

1
4
CORNER WEIGHTS (SMALL CABINET)
018
Unit
lb
kg
Unit Only
290
132
Weight
Corner Weight
75
34
1
Corner Weight
62
28
2
Corner Weight
97
44
3
Corner Weight
56
25
4
Rigging Weight
309
140
Shipping
344
156
Weight
Step 6—Connect Condensate Drain
NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 48SD disposes of condensate water through a 3/4 in. NPT
fitting which exits through the base on the evaporator coil access
side. See Fig. 3 & 4 for location.
Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground
level installations. Install a field- -supplied 2- -in. condensate trap at
the end of condensate connection to ensure proper drainage. Make
sure that the outlet of the trap is at least 1 in. (25 mm) lower than the
drain- -pan condensate connection to prevent the pan from
overflowing (See Fig. 7). Prime the trap with water. When using a
gravel apron, make sure it slopes away from the unit.
1" min.
Fig. 7 - - Condensate Trap
Connect a drain tube using a minimum of 3/4- -in. PVC or 3/4- -in.
copper pipe (all field- -supplied) at the outlet end of the 2- -in. trap.
Do not undersize the tube. Pitch the drain tube downward at a slope
of at least 1- -in. (25 mm) for every 10 ft (3 m) of horizontal run. Be
sure to check the drain tube for leaks.
Step 7—Install Flue Hood
The flue assembly is secured and shipped in the return air duct.
Remove duct cover to locate the assembly (See Fig. 9 and 10).
NOTE: Dedicated low NOx models MUST be installed in
California Air Quality Management Districts where a Low NOx
rule exists.
2
3
C00070b
024
030
lb
kg
lb
kg
343
156
355
161
360
69
31
75
34
53
24
56
25
83
38
81
37
138
63
143
65
145
353
160
365
166
370
383
173
395
179
400
Fig. 6 - - 48SD Unit Corner Weights and Suggested Rigging
TRAP
OUTLET
2" min.
C00009
DETAIL A
036
Unit
lb
kg
Unit Only
163
Weight
Corner Weight
74
34
1
Corner Weight
55
25
2
Corner Weight
86
39
3
Corner Weight
66
4
168
Rigging Weight
Shipping
181
Weight
These models meet the California maximum oxides of nitrogen
(NOx) emissions requirements of 40 nanograms/joule or less as
shipped from the factory.
NOTE: Low NOx requirements apply only to natural gas
installations.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
The venting system is designed to ensure proper venting. The
flue hood assembly must be installed as indicted in this section
of the unit installation instructions.
Install the flue hood as follows:
1. This installation must conform with local building codes and
with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in
Canada, CAN/CGA B149.1, and B149.2) or NFPA
(National Fire Protection Association) latest revision. Refer
to Provincial and local plumbing or wastewater codes and
other applicable local codes.
2. Remove flue hood from shipping location (inside the return
section of the blower compartment- -see Fig. 9 & 10). Re-
move the return duct cover to locate the flue hood. Place flue
hood assembly over flue panel. Orient screw holes in flue
hood with holes in the flue panel.
3. Secure flue hood to flue panel by inserting a single screw on
the right side and the left side of the hood.
8
CORNER WEIGHTS (LARGE CABINET)
042
048
lb
kg
lb
kg
450
204
480
218
90
41
97
44
72
33
74
34
110
50
116
53
178
81
193
88
465
211
495
225
510
231
540
245
WARNING
A05161
060
lb
kg
484
220
98
45
75
34
118
54
193
88
499
226
544
247