Carrier 40MB*C Installation Instructions Manual page 13

Cassette ductless split system system sizes 09"" 18 air conditioner
Hide thumbs Also See for 40MB*C:
Table of Contents

Advertisement

3.3
Purging air and checking
gas leakage
[] When piping work is completed,
it is necessary to purge the
air and check for gas leakage.
,_
WARNING
[] Do not mix any substance
other than the specified
refrigerant
into the refrigeration
cycle.
[] When refrigerant gas leaks occur, ventilate the room as soon as
possible.
[] The specified
refrigerant should always be recovered
and never
be released directly into the environment.
[] Use a vacuum pump for the specified
refrigerant.
Using the
same vacuum pump for different refrigerants
may damage the
vacuum pump or the unit.
[]
If using additional
refrigerant,
perform air purging from the
refrigerant pipes and indoor unit using a vacuum pump, then
charge additional refrigerant.
[]
Use a hexagonal
wrench(4mm/0.2in)
to operate the stop valve
rod.
[] All refrigerant
pipe joints should be tightened with a torque
wrench at the specified tightening
torque.
Compound
pressuregauge
Pressure metre
Gauge
Gas st0pvalve
manifold
Low-pressure
valve
Chan
hoses
Vacuum pump
Service port
Liquidstop valve
1) Connect the projection
side of charging hose (which comes from
the gauge manifold) to gas stop valve's service port.
2)
open gauge fully the manifold's
low-pressure
valve (Lo) and
completely
close its high-pressure
valve (Hi)
(High-pressure
valve subsequently
requires no operation.)
3) Perform vacuum pumping and ensure that the compound
pressure gauge reads -0.1MPa (=76cmHg).* 1
4) Close the gauge manifold's
low-pressure
valve (Lo) and stop
the vacuum
pump.
(maintain this state for a few minutes to make sure that the
compound
pressure gauge pointer does not swing back.)*2
5) Remove caps from liquid stop valve and gas stop valve.
6) Turn the liquid stop valve's rod 90 degrees counterclockwise
with a hexagonal
wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit's
flare and outdoor unit's flare and valve rods.
After the check is complete,
wipe all soapy water off.
7) Disconnect
charging hose from gas stop valve's service port
then fully open liquid and gas stop valves.
(Do not attempt to turn valve rod byond its stop.)
8) Tighten valve caps and service port caps for the liquid and
gas stop valves with a torque wrench at the specified
torques.
"1. Pipe length vs. Vacuum
pump run time
Pipe length
Up to 49.2ft/I 5m
More than 49.2ft/I 5m
Run time
Not less than I0 min
Not less than 15min
*2. If the compound
pressure
gauge
pointer
swings
back,
refrigerant
may have water content
or a loose pipe joint may
exist. Check all pipe joints and retighten
nuts as needed,
then repeat steps 2) through
4).
3.4
Nil
[]
Additional
refrigerant
charge
CAUTION
Refrigerant
may only be charged after performing
the leak
test and the vacuum pumping.
Check the type of refrigerant
needed on the machine
nameplate.
Charging with an unsuitable
refrigerant
may
cause explosions
and accidents,
so always ensure that the
appropriate
refrigerant is charged.
Refrigerant
containers
shall be opened slowly.
[] The outdoor unit is factory charged with refrigerant.
Calculate the
added refrigerant according
to the diameter and the length of the
liquid pipe of the outdoor unit/indoor
unit connection.
Pipe length
and refrigerant
amount:
Connective
Air purging
pipe length
method
Additional amount of refrigerant to be charged
Less
Use vacuum
than
pump.
25ft/7.5m
Use vacuum
More
than
pump,
25ft/7.5m
Liquid side:aP 1/4in / 6.35mm
R410A: (Pipe length- 25(7.5))x 0.16oz/ft (15g/m)
Liquid side: #p3/8in / 9.52mm
R410A: (Pipe length-25(7.5))x0.32oz/ft(30g/m
)
[] Be sure to add the proper amount of additional
refrigerant.
Failure to do so may result in reduced performance.
3.5
Refrigerant
piping work
1) Caution
on the pipe handling
[]
Protect the open end of the pipe against dust and moisture.
[]
All pipe bends should be as gentle as possible.
Use a pipe
bender for bending.
Rain
I I',
r
[
Be sure to
place a cap.
If no flare cap is
available, cover the
flare mouthwith
tape to keep dirt or
water out.
Wall
13

Advertisement

Table of Contents
loading

Table of Contents