MILLIVOLT: CHECK GAS PRES SURE AND ELECTRICAL INSTALLATION

CHECK GAS PRESSURE

1. Check gas type. The gas supply must be the same as
stated on the appliance's rating decal. If the gas supply
is different from the fi replace, STOP! Do not install the
appliance. Contact your dealer immediately.
2. To ease installation, a 24" (610 mm) fl ex line with manual
shut-off valve has been provided with on this appliance.
Install and attach 3/8" gas line onto shut-off valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
fi replace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.
4. To adjust fl ame height, turn HI/LO knob to HI to get
maximum pressure to burner. Turn HI/LO knob to LO
to get minimum pressure. NOTE: To make the process
of checking the gas pressure easier, unfasten the two
screws which secure the gas valve to the side of the
fi rebox and bring forward. [Remove the glass to allow
the valve to come forward. (Refer to Page 45 for glass
removal.)] When done, you must refasten the gas valve
into place.
5. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
Figure 29. After taking pressure reading, be sure and
turn captured screw clockwise fi rmly to reseal. Do not
over torque. Check test points for gas leaks.

ELECTRICAL WIRING

This fi replace will work without any electrical supply. Elec-
tricity is only needed to operate the blower and the light
located behind the logs inside the fi rebox.
NOTE: If installed in mobile home, fi replace must be bolted
securely to fl oor.
Verify proper operation after servicing.
Electrical connections should only
be performed by a qualified, licensed
electrician. Main power must be off when
connecting to main electrical power supply
or performing service. All wiring shall be
in compliance with all local, city, and state
codes. The appliance, when installed, must
be electrically grounded in accordance with
local codes, or in the absence of local codes,
with the National Electrical Code ANSI/ NFPA
70 (latest edition) and Canadian Electrical
Code, CSA C22.1.
20306742
KHLDV Series Gas Fireplace
Pressure
Test "IN"
Pressure
Test "OUT"
HI/LO Knob
Pilot Adjustment
Screw
Figure 29 -
Gas Pressure Check at Gas Valve
Do not use open fl ame to check
for gas leaks.
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
FP1979
23