FIREPLACE INSTALLATION

CHECK GAS TYPE

Use proper gas type for the fi replace you are installing.
If you have confl icting gas type, do not install fi replace.
See dealer where you purchased the fi replace for proper
fi replace for your gas type or conversion kit.
INSTALLING GAS PIPING TO FIREPLACE /
BURNER SYSTEM LOCATION
A qualifi ed installer or service person
must connect appliance to gas supply.
Follow all local codes.
INSTALLATION ITEMS NEEDED
Before installing fi replace and burner system, make sure
you have the items listed below.
Test gauge connection*
Equipment shutoff valve*
Sediment trap (recommended)
External regulator (supplied by installer)
Piping (check local codes)
Sealant (resistant to propane/LP gas)
Approved fl exible gas line with gas connector (if
allowed by local codes — not provided)
* A CSA design-certifi ed equipment shutoff valve with 1/8"
NPT tap is an acceptable alternative to test gauge connec-
tion. Purchase the CSA design-certifi ed equipment shutoff
valve from your dealer.
For propane/LP connections only, the installer must supply
an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas
pressure to between 11 and 13 inches of water. If you do
not reduce incoming gas pressure, burner system regulator
damage could occur. Install external regulator with the vent
pointing down as shown in Figure 27. Pointing the vent
down protects it from freezing rain or sleet.
For propane/LP units, never connect
fi replace directly to the propane/LP supply.
This burner system requires an external
regulator (not supplied). Install the external
regulator between the burner system and
propane/LP supply.
20306742
Tee joint
Pipe wrench
KHLDV Series Gas Fireplace
External
Regulator
Figure 27 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
Use only new black iron or steel pipe.
Internally tinned copper or copper tubing
can be used per National Fuel Code, section
2.6.3, providing gas meets hydrogen sulfi de
limits, and where permitted by local codes.
Gas piping system must be sized to provide
minimum inlet pressure (listed on data plate)
at the maximum fl ow rate (BTU/hr). Undue
pressure loss will occur if the pipe is too
small.
When using copper of fl ex connectors use only fi ttings
approved for gas connections. The gas control inlet is
3/8" NPT.
100 gallon (min)
Propane/LP
Supply Tank
Vent Pointing
Down
FP1977
21