Table 9-3 Warning Message - Delta RPI-M8 User Manual

Grid-tied solar inverter
Hide thumbs Also See for RPI-M8:
Table of Contents

Advertisement

1. Actual Solar1 voltage is over
1000Vdc
Solar1 High
2. Detection circuit malfunction
1. Actual Solar2 voltage is over
1000Vdc
Solar2 High
2. Detection circuit malfunction
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Insulation
Minus to Ground or both.
3. Detection circuit malfunction
Warning
Message
Possible cause
1. Actual Solar1 voltage is
under the limit
2. Some devices were
damaged inside the inverter
Solar1 Low
if the actual Solar1 voltage is
close to "0"
3. Detection circuit malfunction
1. Actual Solar2 voltage is
under the limit
2. Some devices were
damaged inside the inverter
Solar2 Low
if the actual Solar2 voltage is
close to "0"
3. Detection circuit malfunction
1. One or more fans are locked
2. One or more fans are
defective
HW FAN
3. One ore more fans are
disconnected
3. Detection circuit malfunction
1. Modify the solar array setting, and make the
Voc less than 1000Vdc
2. Check the detection circuit inside the inverter
1. Modify the solar array setting, and make the
Voc less than 1000Vdc
2. Check the detection circuit inside the inverter
1. Check the insulation of Solar inputs
2. Check the capacitance, dry PV panel if
necessary
3. Check the detection circuit inside the inverter

Table 9-3 Warning Message

1. Check the Solar1 voltage connection to the
inverter terminal
2. Check all switching devices in boost1
3. Check the detection circuit inside the inverter
1. Check the Solar2 voltage connection to the
inverter terminal
2. Check all switching devices in boost2
3. Check the detection circuit inside the inverter
1. Remove the object that stuck in the fan(s)
2. Replace the defective fan(s)
3. Check the connections of all fans
4. Check the detection circuit inside the inverter
Action
55