AC's wiring can be separated into 3-phase and PE (3P3W) or 3-phase, N, and
PE (3P4W). Only some models can support 3P3W system. Please refer to table
5-3. The following instruction is based on 3P4W. If the grid system is 3P3W,
please ignore the description of N.
CAUTION! Machine and equipment damage may occur.
◆ Make sure to choose the correct wire size AC cable.
◆ Failure to follow these instructions may cause AC plug
Follow the steps below to strip the wires before assembling the AC plug:
a) Trim the L1, L2, L3, and N wire to 52.5 mm (2.0 inch).
b) Strip 12 mm (0.5 inch) of insulation from all wire ends.
c) Remove 55 mm (2.2 inch) of AC cable outer jacket.
damage.
Figure 5-3 Stripping the wire